Performing a good system start-up is crucial to having a long lasting system that will be trouble free. A trained, qualied technician that
understands the system’s mechanical and electrical operation must do the system start-up. The system start-up report should be completed
in coordination with the installing contractor, start-up technician, health department agent, homeowner, and the engineer. An installation and
start-up checklist (CL0063) is included to aid the system start-up procedure.
The timed dosing panel should be set up to dose 96 times per day. Consult the engineering site plan and/or control panel instructions to aid
in the set up. Recirculation ratio must be taken into account when adjusting for the daily design ow rate.
The homeowner and maintenance contract personnel must receive a copy of the following documents:
1. Recirculating Media Filter literature sheet (CL0062).
2. Recirculating Media Filter Owner’s Manual (CL0064).
3. Control Panel Wiring Diagram.
4. Control Panel Installation Instructions and Operation/Troubleshooting Manual.
5. Completed Start-Up Report.
6. Tru-Flow
®
Splitter System Installation Instructions (CL0075).
7. Submersible Pump Installation Instructions (FM0447).
8. WW1 Filter owner's manual (CL0040).
Record the oat settings of the dose tank and recirculation basin on the drawings below.
System Start-up
Typical Float Settings For Zoeller Model N153 Pumps
SK2147
MEDIA FILTER DOSE TANK
SK2153
PUMP DISCHARGE BASIN
(locatedinmedialteronpumpdischargesystems)
ON LEVEL
OFF LEVEL
ALARM FLOAT
TETHER HEIGHT
5"
6 1/2"
15"
VERTICAL FLOAT SWITCH
TETHER HEIGHT
21"