Specification
Product Submittal Sheet
Tech Support: 888-437-3244 Sales: 800-543-7140
Engineering Services: 877-832-3206 clarkdietrich.com
Product category:
Product name:
ProSTUD® 20 Drywall Stud
362PDS125-19 65ksi G40EQ - Punched
3-5/8" ProSTUD 20 (19mil)
3-5/8" ProSTUD 20 (19mil) Drywall Stud - COMPOSITE Limiting Heights (AC86-2015)
(1 layer) 5/8" Type X Gypsum Board
Spacing 5 psf 7.5 psf 10 psf
(inches) L/120 L/240 L/360 L/120 L/240 L/360 L/120 L/240 L/360
12 23'-3" 18'-5" 16'-1" 20'-4" 16'-1" 14'-1" 18'-5" 14'-8" 12'-10"
16 21'-1" 16'-9" 14'-8" 18'-5" 14'-8" 12'-10" 16'-7"f 13'-4" 11'-7"
24 18'-5" 14'-8" 12'-10" 15'-8"f 12'-10" 11'-1" 13'-7"f 11'-7" 9'-11"
Composite Table Notes:
• Allowable composite limiting heights were determined in accordance with ICC-ES AC86-2015.
• Additional composite wall testing and analysis requirements of the SFIA Code Compliance Certification Program were observed.
• In accordance with current building codes and AISI design standards, the 1/3 Stress Increase for strength was not used.
• The composite limiting heights provided in the tables are based on a single layer of type X gypsum board from the following manufacturers: American, CertainTeed,
Georgia Pacific, Continental, National, PABCO, and USG.
• The gypsum board must be applied full height in the vertical orientation to each stud flange and installed in accordance with ASTM C754 using minimum No. 6 Type S
Drywall screws spaced as listed below:
• Screws spaced a minimum of 16 in on-center to framing members spaced at 16 in or 12 in on-center.
• Screws spaced a minimum of 12 in on-center to framing members spaced at 24 in on-center.
• No fasteners are required for attaching the stud to the track except as detailed in ASTM C754.
• Stud end bearing must be a minimum of 1 inch.
• f: Adjacent to the height value indicates that flexural stress controls the allowable wall height.
• s: Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.
3-5/8" ProSTUD 20 (19mil) Drywall Stud - NON-COMPOSITE Limiting Heights (FULLY BRACED)
Spacing 5 psf 7.5 psf 10 psf
(inches) L/120 L/240 L/360 L/120 L/240 L/360 L/120 L/240 L/360
12 18'-10" 14'-11" 13'-0" 16'-5" 13'-0" 11'-5" 14'-5" 11'-10" 10'-4"
16 17'-1" 13'-7" 11'-10" 14'-5" 11'-10" 10'-4" 12'-5" 10'-9" 9'-5"
24 14'-5" 11'-10" 10'-4" 11'-9" 10'-4" 9'-0" 10'-2" 9'-5" 8'-3"
Non-Composite Table Notes:
• Heights are based on AISI S100-12, North American Specification, and AISI S220-15, North American Standard for Cold-Formed Steel Framing - Nonstructural Members,
using steel properties alone.
• Above listed Non-Composite Limiting Heights are applicable when the unbraced length is less than or equal to Lu.
• Heights are limited by moment, deflection, shear, and web crippling (assuming 1" end reaction bearing).
• Heights labeled with a "*" can achieve higher heights by using end-bearing stiffeners. See full ProSTUD non-composite charts at clarkdietrich.com.
CD-PDS-LH © 06/17 ClarkDietrich Building Systems