- Diagnosis QUADRANT 2200 / 2200 RC with CCT
- Contents
- 1.0 Control terminal service menu (up to module 1 no. 835024.2)
- 1.1 Service menu structure (up to module 1 no. 835024.2)
- 1.2 Additional information about page "8/1 (Service 1)" (up to module 1 no. 835024.2)
- 1.3 Additional information about page "8/2 (Service RC)" (up to module 1 no. 835024.2)
- 1.4 Input testing (up to module 1 no. 835024.2)
- 1.5 Output testing (up to module 1 no. 835024.2)
- 1.6 Error display (up to module 1 no. 835024.2)
- 1.7 Key test (up to module 1 no. 835024.2)
- 2.0 Control terminal service menu (from module 1 no. 835024.3)
- 2.1 Service menu structure (from module 1 no. 835024.3)
- 2.2 Additional information about page "8/1 (Service 1)" (from module 1 no. 835024.3)
- 2.3 Additional information about page "8/2 (Service RC)" (up to module 1 no. 835024.3)
- 2.4 Input testing (from module 1 no. 835024.3)
- 2.5 Output testing (from module 1 no. 835024.3)
- 2.6 Error display (from module 1 no. 835024.3)
- 2.7 Key test (from module 1 no. 835024.3)
- 3.0 Control terminal service menu (on CCU module)
- 3.1 Service menu structure (on CCU module)
- 3.2 Additional information about page "8/1 (Service 1)" (on CCU module)
- 3.3 Additional information about page "8/2 (Service RC)" (on CCU module)
- 3.4 Input testing (on CCU module)
- 3.5 Output testing (on CCU module)
- 3.6 Error display (on CCU module)
- 3.7 Key test (on CCU module)
- 4.0 Additional information
- 5.0 Information on replacing modules
- 0299 251.2
4.3 General (with central terminal compartment)
The bale length determined by the metering wheel when ejecting bales
is saved in the baler module and added to the next bale later during
baling. This value is stored even after switching off the ignition.
The baling pressure is relieved when the bale is ejected.
Ejecting bales
When the maximum allowed ram force is exceeded, the baling pressure
is abruptly relieved. This shuts down the baling pressure control for 7
seconds. After this, the pre-set baling pressure is built up again.
Overload protection
The knotter is cleaned directly prior to tying the bale and after half the
bale length has been reached.
Knotter cleaning
At a PTO shaft speed of approx. 350 rpm, the speed sensors (drive,
feed rake, rotor) should display a correct value.
Speed sensors
The full scope of electronic functions is available when:
the main switch has been switched on for more than 3 seconds and
the baler speed is at least 500 rpm.
CCT
When the bale length bar in the Control Terminal remains completely
dark and when bale tying is not possible (e.g. by excessively fast
rotation of the metering wheel by hand), the tying release must be reset.
To do this, proceed as follows:
1. With the CCT switched on, turn back metering wheel until bar
stops being dark
2. Wait for approx. 10 s
3. Switch CCT off / on.
Bale length display
To be able to carry out a manual tying start on balers from machine no.,
the metering wheel must have measured a bale length of at least
approx. 40 cm.
Manual tying start
Diagnosis QUADRANT 2200/ 2200 RC TIC
30 08/2002