Specifications
Table Of Contents
- Front cover
- Trademarks
- Contents
- Remedy and measure after a report of error
- I Alarms
- 1. Operation Errors (M)
- 2. Stop Codes (T)
- 3. Servo/Spindle Alarms (S)
- 4. MCP Alarms (Y)
- 5. Safety Observation Alarms (Y)
- 6. System Alarms (Z)
- 7. Absolute Position Detection System Alarms (Z7*)
- 8. Emergency Stop Alarms (EMG)
- 9. Auxiliary Axis Operation Errors (M)
- 10. CNCCPU-side Safety Sequence Alarm(U)
- 11. Multi CPU Errors (A)
- 12. Network Errors (L)
- 13. Program Errors (P)
- II Parameters
- 1. Machining Parameters
- 2. Base Specifications Parameters
- 3. Axis Specifications Parameters
- 4. Servo Parameters
- 5. Spindle Parameters
- 6. Multi-CPU Parameters
- 7. FL-net Parameters
- 8. DeviceNet Parameters
- 9. Machine Error Compensation Parameters
- 10. PLC Parameters
- 11. Macro List
- 12. Position Switches
- 13. PLC Axis Indexing Parameters
- III PLC Devices
- Revision History
- Back cover

I Alarms
Multi CPU Errors (A)
I - 56
A01 MULTI CPU ERROR 3000
Details
- In a multiple CPU system, the intelligent function module under control of another CPU is
specified in the interrupt pointer setting of the PLC parameter.
Remedy
- Specify the head I/O number of the intelligent function module under control of the host CPU.
- Delete the interrupt pointer setting of the parameter.
Details
- The PLC parameter settings for timer time limit setting, the RUN-PAUSE contact, the com-
mon pointer No., number of vacant slots, system interrupt settings or service operation set-
tings are outside the range that can be used by the CPU module.
Remedy
- Read the detailed information of the error using a programming tool, check the parameter
items corresponding to those numerical values (parameter numbers), and correct when nec-
essary.
- If the error is still generated following the correction of the parameter settings, the possible
cause is the memory error of the CPU module's built-in RAM, program memory or the mem-
ory card. Contact your local service center.
Details
- [Memory card (ROM)] is designated as a drive for the file register and "Use the following file"
or "Use the same file name as the program" is selected in the PLC file settings, while ATA
card is actually set to the PC card slot.
Remedy
- Read the detailed information of the error using a programming tool, check the parameter
items corresponding to those numerical values (parameter numbers), and correct when nec-
essary.
- If the error is still generated following the correction of the parameter settings, the possible
cause is the memory error of the CPU module's built-in RAM, program memory or the mem-
ory card. Contact your local service center.
A01 MULTI CPU ERROR 3001
Details
- The parameter settings are corrupted.
Remedy
- Read the detailed information of the error using a programming tool, check the parameter
items corresponding to those numerical values (parameter numbers), and correct when nec-
essary.
- If the error is still generated following the correction of the parameter settings, the possible
cause is the memory error of the CPU module's built-in RAM, program memory or the mem-
ory card. Contact your local service center.
A01 MULTI CPU ERROR 3002
Details
- The designated memory has no file register file, although “Use the following file” and no ca-
pacity have been set for the file register in the PLC parameter, PLC file settings.
Remedy
- Read the detailed information of the error using a programming tool, check the parameter
items corresponding to those numerical values (parameter numbers), and correct when nec-
essary.
- If the error is still generated following the correction of the parameter settings, the possible
cause is the memory error of the CPU module's built-in RAM, program memory or the mem-
ory card. Contact your local service center.
A01 MULTI CPU ERROR 3003
Details
- The number of devices set at the PLC parameter device settings exceeds the possible CPU
module range.
Remedy
- Read the detailed information of the error using a programming tool, check the parameter
items corresponding to those numerical values (parameter numbers), and correct when nec-
essary.
- If the error is still generated following the correction of the parameter settings, the possible
cause is the memory error of the CPU module's built-in RAM, program memory or the mem-
ory card. Contact your local service center.
Details
- The automatic refresh range of the multiple CPU system exceeded the file register capacity.
Remedy
- Change the file register file for the one refresh-enabled in the whole range.
A01 MULTI CPU ERROR 3004
Details
- The parameter file is incorrect.
Alternatively, the contents of the file are not parameters.
Remedy
- Check whether the parameter file version is ***QPA, and check the file contents to be sure
they are parameters.
A01 MULTI CPU ERROR 3012
Details
- Multiple CPU setting or control CPU setting differs from that of the reference CPU settings
in a multiple CPU system.
Remedy
- Match the multiple CPU setting or control CPU setting in the PLC parameter with that of the
reference CPU (CPU No.1) settings.