Specifications

Table Of Contents
Remedy and measure after a report of error
<Preparation>
- Confirm that the operation history of alarm diagnosis is set to "P: Execute" so that the error data can
be collected. Error data can be kept in this state. The back ground of "P: Execute" is reversed in white.
- After having collected error data, return the operation history to "P: Execute".
<Sequence of remedy and measure>
IMPORTANT
1. Take a detailed note of the operations applied just before the error occurrence.
2.Operation history is regularly updated. Therefore, interruption should be carried out just after the error
occurrence.
(1) Select [HISTORY] in the alarm diagnosis.
Set [I] in #( ) and press enter. The oper-
ation history will be interrupted.
Display 1 shows the stop state.
The back ground of the operation history
is turned white.
(2) Select [COORDI] on monitor. Note down
value of coordinates, programming num-
ber under the operation, etc.
Note down the information on display 2.
(3) Collect SRAM.BIN data in CNC data in-
put function.
Refer to display 3
(a) Function: Select "COPY"
(b) Device: Select "CNC"
(c) Directory: Select "Mainte data”
(d) File name: Select "SRAM.BIN"
(e) Scroll down to under the arrow.
(f) Device: Select the output destination
for the above data.
(g) Press [Exec] on the bottom right.
(4) Select ""Backup function (Device->GOT)" to collect PC CPU data and CNC CPU data with the
restored backup function.
(5) Provide us with the SRAM.BIN and the restored backup data.