Specifications
Table Of Contents
- Front cover
- Trademarks
- Contents
- Remedy and measure after a report of error
- I Alarms
- 1. Operation Errors (M)
- 2. Stop Codes (T)
- 3. Servo/Spindle Alarms (S)
- 4. MCP Alarms (Y)
- 5. Safety Observation Alarms (Y)
- 6. System Alarms (Z)
- 7. Absolute Position Detection System Alarms (Z7*)
- 8. Emergency Stop Alarms (EMG)
- 9. Auxiliary Axis Operation Errors (M)
- 10. CNCCPU-side Safety Sequence Alarm(U)
- 11. Multi CPU Errors (A)
- 12. Network Errors (L)
- 13. Program Errors (P)
- II Parameters
- 1. Machining Parameters
- 2. Base Specifications Parameters
- 3. Axis Specifications Parameters
- 4. Servo Parameters
- 5. Spindle Parameters
- 6. Multi-CPU Parameters
- 7. FL-net Parameters
- 8. DeviceNet Parameters
- 9. Machine Error Compensation Parameters
- 10. PLC Parameters
- 11. Macro List
- 12. Position Switches
- 13. PLC Axis Indexing Parameters
- III PLC Devices
- Revision History
- Back cover

I Alarms
System Alarms (Z)
I - 40
Z89 APLC ERROR 0001
Details
C language module is not adequately stored in NC in APLC release.
Remedy
Resend the C language module.
Z89 APLC ERROR 0002
Details
SRAM size exceeded 16KB in APLC release.
Remedy
Make the SRAM size to 16KB or smaller.
Z89 APLC ERROR 0003
Details
DRAM size exceeded 512KB in APLC release.
Remedy
Downsize the DRAM to 512KB or smaller.
Z89 APLC ERROR 0004
Details
APLC module does not include initialize function aplc_top, dramSizeCheck, sramSizeCheck,
or setUserBaseMain.
Remedy
Check if APLC module includes the above functions.
Z89 APLC ERROR 0005
Details
The contents of APLC module in FROM is illegal and cannot be loaded.
Remedy
Check the contents of APLC module.
* Check if it does not include an undefined function."
Z89 APLC ERROR 0006
Details
APLC was activated during APLC invalid mode.
Remedy
Change to APLC valid mode.
Z99 FILE AREA ERROR 0001
Details
The edited data is destroyed probably because it was not properly updated and the backup
operation did not complete normally.
Remedy
Format the area again.
Z99 FILE AREA ERROR 0002 (month, date)
Details
There was a high possibility that the edited data was not properly updated so that it was re-
covered using the backup data.
The machining program is not the newest.
Remedy
Check the machining program you were editing, and edit it again if it is same as the one before
being edited.
This alarm will be canceled by turning ON the edit data recovery signal after recovering work
is completed.
"Emergency stop DATA" will be canceled by turning the controller ON again.
The data when the recovered data was backuped will be displayed in four digits (month and
date) behind the error No., as a rough idea for data recovery.
Z99 FILE AREA ERROR 0003
Details
The edit work just before the power went down may not be reflected.
When the program capacity 2560m/1520m is set as option, the file will be compressed and
saved after the program edit. The power supply for NC was cut during compressing the file.
Remedy
Check the machining program you were editing, and edit it again if it is same as the one before
editing.
This alarm will be canceled by turning ON the edit data recovery signal after recovering work
is completed.
"Emergency stop DATA" will be canceled by turning the controller ON again.
Keep NC ON during the file compressing. This operation takes thirty seconds maximum.
Z99 FILE AREA ERROR 0004
Details
The compressed data does not fit in the memory.
Remedy
Delete unnecessary data and edit it again.
If the power is turned ON again while the error still appears, the program revert to the status
before the error occurred.
Z99 FILE AREA ERROR 0005
Details
Data cannot be uncompressed normally at power ON.
Remedy
Format the area again. Contact the service center.
Z99 FILE AREA ERROR 0006
Details
Memory necessary for edited data or compression cannot be allocated.
Remedy
Contact the service center.