Specifications

36
RF SOLUTION-CITEL
Choosing the SPD technology
DS surge protectors are based on Varistor (MOV) technology.
Some versions use different electrical diagrams :
-
<<
VG
>>
technology : this Gas tube-Varistor hybrib association,
used in Type 1 SPD (DS150VG, DS250VG, DUT250VG),
improves the protection level Up and the residual voltage Ures.
- Association with RFI filter : The Surge protection panel CBB
and secondary SPD DS-HF combine surge protection stage
and filter stage in order to improve the protection level.
Coordination of Surge Protectors
In order to bring maximum protection efficiency, it could be
necessary to create a
<<
coordination
>>
diagram, that means
installation of a
<<
primary
>>
SPD at the network entrance and a
<<
secondary
>>
close to sensitive equipment.
This association is required in the 2 following cases :
- High sensitivity equipment :
󳃨
Improvement of protection level.
-
Long distance (greater than 30m) of wire between equipment
to be protected and primary SPD :
󳃨
Reduction of ringing voltages created during the surge
transmission.
Efficient SPD coordination is performed by including
between primary and secondary SPDs :
- a minimum length of wire (> 10 m).
or
- a coordination inductor (DSH range).