Datasheet

A-6
Catalyst 6500 Series Switches Installation Guide
OL-5781-05
Appendix A Power Supply Specifications
950 W AC-Input and DC-Input Power Supplies
Branch circuit requirement (AC-input) Each chassis power supply should have its own
dedicated, fused-branch circuit:
For North America—15 A
For International—Circuits sized to local and
national codes
All Catalyst 6500 series AC-input power supplies
require single-phase source AC.
All AC power supply inputs are fully isolated.
Source AC can be out of phase between
multiple power supplies in the same chassis,
which means that PS1 can be operating from
phase A and PS2 can be operating from
phase B.
For high-line operation, the power supply
operates with the hot conductor wired to a
source AC phase and the neutral conductor
wired either to ground or to another source AC
phase as long as the net input voltage is in the
range of 170 to 264 VAC.
Source AC can be out of phase between AC
inputs on power supplies that are equipped
with multiple AC inputs, which means that
power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.
Power supply output capacity 950 W maximum (100–240 VAC)
DC-input voltage –48 VDC to –60 VDC continuous
DC-input current
38 A @ –48 VDC
30 A @ –60 VDC
Power supply output (AC supply)
15 A @ +1.5 V
2.5 A @ +3.3 V
19.15 A @ +50 V
Power supply output (DC supply)
15 A @ +1.5 V
2.5 A @ +3.3 V
19.15 A @ +50 V
Table A-3 950 W AC-Input and DC-Input Power Supplies Specifications (continued)
Item Specification