Appendix A Power Supply Specifications
6000 W AC-Input Power Supply
Branch circuit requirement (AC-input) Each power supply input should have its own
dedicated, fused-branch circuit:
• For North America—20 A
• For International—Circuits should be sized
according to local and national codes
• All Catalyst 6500 series AC-input power supplies
require single-phase source AC.
• All AC power supply inputs are fully isolated.
–
Source AC can be out of phase between
multiple power supplies in the same chassis,
which means that PS1 can be operating from
phase A and PS2 can be operating from
phase B.
–
For high-line operation, the power supply
operates with the hot conductor wired to a
source AC phase and the neutral conductor
wired either to ground or to another source AC
phase as long as the net input voltage is in the
range of 170 to 264 VAC.
–
Source AC can be out of phase between AC
inputs on power supplies that are equipped
with multiple AC inputs, which means that
power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.
Power supply output
• 2900 W operation (one 220 VAC source or two
110 VAC sources)
–
25 A @ +3.3 V
–
12 A @ +12 V
–
63.6 A @ +42 V
• 6000 W operation (two 220 VAC sources)
–
25 A @ +3.3 V
–
12 A @ +12 V
–
137.4 A @ +42 V
Output holdup time 20 ms minimum
Heat dissipation 23,812 BTU/hour (approx.)