Power-Supply Input
Receptacles
IEC 320-C14
(IEC60320-
C14)
IEC 320-C14
(IEC60320-
C14)
IEC 320-C13
(IEC60320-
C14)
IEC 320-C13
(IEC60320-
C14)
Power Cord Rating 15A 15A 15A 12A@-
100VDC
10A 12AWG
Description Specifications
WS-C3560E-
48PD-SF
WS-C3560E-
24PD-S
WS-C3560E-
48PD-S
WS-C3560E-
24TD-S
WS-C3560E-
48TD-S
C3K-PWR-
1150WAC
C3K-PWR-
750WAC
C3K-PWR-
265WAC
C3K-PWR-
265WDC
C3K-PWR-
300WAC
100% Throughput
Measured Power
Consumption
146W 89W 133W 89W 151W
Measured Output
BTU/hr
498 303 451 303 514
5% Throughput
Measured Power
Consumption
137W 94W 124W 96W 141W
Measured Output
BTU/hr
466 320 420 292 481
5% Throughput (with 50% PoE loads)
Measured Power
Consumption
Switch Power:
558W
PoE Power: 385W
Switch Power:
297W
PoE Power: 193W
Switch Power:
332W
PoE Power: 196W
N/A N/A
Measured Output
BTU/hr
At the Switch: 590 At the Switch: 355 At the Switch: 464 N/A N/A
100% Throughput (with maximum possible PoE loads)
Measured Power
Consumption
Switch Power:
972W
PoE Power: 744W
Switch Power:
502W
PoE Power: 372W
Switch Power:
540W
PoE Power: 375W
N/A N/A
Measured Output
BTU/hr
At the Switch: 778 At the Switch: 443 At the Switch: 561 N/A N/A
Note:
Disclaimer: All power consumption numbers were measured under controlled laboratory conditions
and are provided as an estimate.
The wattage rating on the power supply does not represent actual power draw. It indicates the
maximum power draw possible by the power supply. This rating can be used for facility capacity
planning. For PoE switches, cooling requirements are smaller than the actual power consumption
as a significant portion of PoE loads are dissipated in the end points
Non-PoE Power Consumption
100 Percent Throughput Switch Power Consumption
The numbers indicate the power consumed by a typical switch under normal conditions. Normal
conditions signify a temperature of 25 degrees Celsius, atmospheric pressure in the range of 860
to 1060 mbar and relative humidity from 30 to 75 percent. Typically such power draws are only
seen when encountering a 100 percent traffic load made up entirely of 64 byte packets on the
switch and the uplinks.
5 Percent Throughput Switch Power Consumption
The numbers indicate the power consumed by a typical switch under normal conditions. Normal
conditions signify a temperature of 25 degrees Celsius, atmospheric pressure in the range of 860