Installing the Power Feed Panel
Attaching the Ground Lug
A ground lug kit is provided with the power feed panel. Use the following steps to attach the ground lug
to the power feed panel chassis.
Step 1 Attach an approved ground wire to the ground lug.
Step 2 Locate the two ground lug threaded holes on the upper right of the rear panel.
Step 3 Align the ground lug with the threaded holes and fasten it to the chassis using the two screws included
in the kit. (See Figure 19.)
Figure 19 Attaching the Ground Lug
Step 4 Using a number 2 Phillips screwdriver, tighten the screws.
Wiring the DC Power
Follow the procedures in this section to wire the DC power.
Note The color coding of DC-input power supply leads depends on the color coding of the DC power
source at your site. Typically, green or green/yellow is used for ground, black is used for +48V
(return), and red or white is used for –48V. Make certain the lead color coding you choose for the
DC-input power supply matches lead color coding at the DC power source.
Note The length of the cable between the –48v power supply and the power feed panel must not exceed
9.4 feet (3m).
Warning
This product requires short-circuit (overcurrent) protection to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations. To see
translations of the warnings that appear in this publication, refer to the “Regulatory Compliance
and Safety Information” section in this document.
Warning
This equipment has a connection between the earthed conductor of the DC supply circuit and the
earthing conductor.
1) This equipment shall be connected directly to the DC supply system earthing electrode conductor
or to a bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing
electrode is connected.