Cisco uBR7200 Series Universal Broadband Router Wireless Modem Card and Subsystem Installation and Configuration
78-6030-03
Installing the Power Feed Panel
Wall-Mounting the Power Feed Panel
To wall-mount the unit, use the same brackets as those used to install the power feed panel in an
equipment rack.
Use the following steps to wall-mount the power feed panel:
Step 1 Attach the brackets to both sides of the power feed panel. (See Figure 17.)
Figure 17 Attaching the Wall Mount Brackets
Step 2 Attach the power feed panel to the wall (see Figure 18), using screws and anchors you provide. To best
support the power feed panel and cables, make sure the power feed panel is attached securely to a
vertical wall stud or to a firmly attached plywood mounting backboard. This position will prevent the
unit from pulling away from the wall when the cables are attached.
Note To meet safety requirements, the power feed panel must be installed with the rear panel
connectors facing up.
Figure 18 Wall-Mounting the Power Feed Panel