Chapter 4 Installation and Startup
Pre-Installation Requirements
SCE 1000 2xGBE Release 2.0.10 User Guide
4-4 OL-7117-02
The environmental monitoring functionality in the SCE 1000 protects the system and components
from potential damage from over-voltage and over-temperature conditions. To ensure normal
operation and to avoid unnecessary maintenance, plan your site configuration and prepare your
site before installation. After installation, make sure the site maintains an ambient temperature of
23
o
F (–5
o
C) through 131
o
F (55
o
C), and keep the area around the SCE 1000 chassis free from dust.
Planning a proper location for the SCE 1000 and the layout of your equipment rack or wiring
closet is essential for successful system operation. Equipment placed too close together or
inadequately ventilated can cause system over-heating. In addition, chassis panels made
inaccessible by poor equipment placement can make system maintenance difficult. The following
precautions can help avoid problems during installation and ongoing operation.
Airflow
Figure 4-2: Airflow Through the SCE 1000
When you plan the location and layout of your equipment rack or wiring closet you need to
consider how air flows though your system. The SCE 1000 draws cooling air in through the
intake vents on the left side of the chassis, moves the air across the internal components, and out
through the right side and rear panel of the chassis. The above figure illustrates the airflow
through the SCE 1000.