Datasheet

A-61
Catalyst 6500 Series Switches Installation Guide
OL-5781-07
Appendix A Power Supply Specifications
8700 W AC-Input Power Supply
Remote Power-Cycling Operation
This feature allows you to remotely power cycle the Catalyst 6500 series switch using any appropriate
third-party relay controller. This eliminates the need for you to have access to the supervisor engine
console or CLI to control power cycling. Table A-40 lists the relay controller box relay type, the
corresponding power supply terminal block positions, and a description of the power-cycling operation.
Table A-40 8700 W Power Supply Relay Controller Switch Settings and Operation
External Relay
Controller Box Relay
Type
Power Supply Relay
Controller Switch
Setting
Power Supply Terminal
Block Positions Used
Remote Power-Cycling Operation
Normally open (NO)
relay.
NO RELAY
(DEFAULT)
Control wires from the
external relay controller
box attach to terminal
block positions 1 and 2.
Power supply cycled from on to off—The
power supply is powered off by energizing
the relay (relay contacts go from open to
closed) for more than 30 seconds.
Power supply cycled from off to on—The
power supply is powered on by deenergizing
the relay (relay contacts go from closed to
open) for more than 10 seconds.
Normally closed (NC)
relay.
NC RELAY Control wires from the
external relay controller
box attach to terminal
block positions 2 and 3.
Power supply cycles from on to off—The
power supply is powered off by energizing
the relay (relay contacts go from closed to
open) for more than 30 seconds.
Power supply cycles from off to on— The
power supply is powered on by deenergizing
the relay (relay contacts go from open to
closed) for more than 10 seconds.
No relay attached.
Remote power-cycling
feature not installed.
NO RELAY
(DEFAULT)
——