Specifications
7-7
Cisco ONS 15454 and Cisco ONS 15327 TL1 Command Guide, R3.3
May 2002
Chapter 7 TL1 Alarms and Errors
Alarms
7.1.13 G1000
An Ethernet line on a G1000 (ONS 15454 only)
7.1.14 NE
The entire network element (SYSTEM)
Table 7-13 G1000
NE Alarm
Severity
(Active) Description
CARLOSS MA/SA A carrier loss on the LAN is the data equivalent of a SONET LOS
alarm. The Ethernet card has lost its link and is not receiving a valid
signal.
TPTFAIL MA/SA Indicates a break in the end-to-end Ethernet link integrity feature of the
G1000-4 cards. This alarm indicates a far-end condition and not a
problem with the port reporting TPTFAIL.
Ta b l e 7- 1 4 N E
NE Alarm
Severity
(Active) Description
BLSROSYNC MA/SA The mapping table needs updating.
DATAFLT MI/NSA The database exceeded the capacity of the flash memory on the
TCC+/XTC.
EHIBATVG-A MA/SA The voltage level on battery lead A exceeds -56.7 Vdc.
(ONS 15454)
EHIBATVG-B MA/SA The voltage level on battery lead B exceeds -56.7 Vdc.
(ONS 15454)
ELWBATVG-A MA/SA The voltage on battery feed A is extremely low or has been lost, and
power redundancy is no longer guaranteed. (ONS 15454)
ELWBATVG-B MA/SA The voltage on battery feed B is extremely low or has been lost, and
power redundancy is no longer guaranteed. (ONS 15454)
HITEMP CR/SA The temperature of the ONS 15454/ONS 15327 is above 50 degrees
Celsius (122 degrees Fahrenheit).
PRC-DUPID MA/SA Two identical node IDs exist in the same ring.
PWR-A MA/SA This alarm applies to the NE rack. It is raised when there is no
power supplied to the main power connector or if power is
connected to the backup power connector (Connector B) but not to
Connector A. (ONS 15454)
PWR-B MA/SA This alarm applies to the NE rack. It is raised when there is no
power supplied to the backup power connector or if power is
connected to the main power connector (Connector A) but not to
Connector B. (ONS 15454)