Current Component Current Value
Rated line voltage: 100-127 VAC; 50 or 60 Hz
Input current (amps) 0.98 (idle)
1.64 (maximum measured)
7.8 (system rated)
60 (peak inrush current; 4 ms)
Leakage current (mA) 0.94 (idle; maximum measured; system rated)
Power (watts) 115 (idle)
191 (maximum measured)
780 (system rated)
VA rating (VA) 118 (idle)
194 (maximum measured)
797 (system rated)
BTU rating (BTU/hr) 392 (idle)
652 (maximum measured)
2661 (system rated)
Rated line voltage: 200-240 VAC; 50 or 60 Hz
Input current (amps) 0.56 (idle)
0.92 (maximum measured)
3.9 (system rated)
60 (peak inrush current; 4 ms)
Leakage current (mA) 0.94 (idle; maximum measured; system rated)
Power (watts) 114 (idle)
189 (maximum measured)
780 (system rated)
VA rating (VA) 117 (idle)
191 (maximum measured)
797 (system rated)
Input requirements
*
BTU rating (BTU/hr) 389 (idle)
644 (maximum measured)
2661 (system rated)
Power supply output power Rated steady-state power 675W
Operating 50 to 95°F (10 to 3C)
at 0-3000 ft (0-914.4m)
with an altitude de-rating of
1.4°F (0.75°C) per 1000 ft (304.8m)
Nonoperating 50 to 109.4°F (10 to 43°C)
Temperature range
Shipment -40 to 140°F (-40 to +60°C)
Relative humidity
(RH; noncondensing)
Operating
Shipment
8 to 80%
5 to 100%
Maximum altitude 7000 ft 2133m
Acoustic noise Operating minimum L WAd (bels) 6.5
Airflow (cubic feet per minute) 30 CFM minimum 75 CFM maximum
Remote management IBM IMM with Virtual Media enabled
*
Maximum measured values were determined with 25ºC ambient temperature, and your results may vary.
*
Idle power: Power drawn with the machine(s) logged into the OS, and no other applications running. Memory, HDDs, optical
drives, and tape drives are not being used.
*
Measured maximum power: Maximum measured power is the power drawn by the machine with the CPUs 100-percent used
and memory is used 10 percent more than base usage. The exerciser used is Prime95 (torture test) and can be downloaded
from
http://www.mersenne.org.
*
Rated system maximum: The maximum power able to be drawn by the machine according to the system label rating.