Datasheet

Data Sheet
© 2010 Cisco and/or its affiliates. All rights reserved. This document is Cisco Public Information. Page 3 of 5
Component Value
Leakage current (mA) 0.47 (idle; maximum measured; system rated)
Power (watts) 68 (idle)
174 (maximum measured)
351 (system rated)
VA rating (VA) 70 (idle)
178 (maximum measured)
351 (system rated)
BTU rating (BTU/hr) 232 (idle)
594 (maximum measured)
2047 (system rated)
Rated line voltage: 200-240 VAC; 50 or 60 Hz
Input current (amps) 0.33 (idle)
0.82 (maximum measured)
3.0 (system rated)
40 (peak inrush current; 4 ms)
Leakage current (mA) 0.47 (idle; maximum measured; system rated)
Power (watts) 67 (idle)
171 (maximum measured)
351 (system rated)
VA rating (VA) 68 (idle)
175 (maximum Measured)
351 (system rated)
BTU rating (BTU/hr) 229 (Idle)
583 (maximum Measured)
2047 (system rated)
Power supply output power Rated steady-state power 351W
Operating 50 to 95°F (10 to 3C)
at 0-3000 ft (0-914.4m)
with an altitude de-rating of
1.4°F (0.75°C) per 1000 ft (304.8m)
Nonoperating 50 to 109.4°F (10 to 43°C)
Temperature range
Shipment -104 to 14F (-40 to 60°C)
Relative humidity (RH;
noncondensing)
Operating
Shipment
8 to 80%
8 to 80%
Maximum altitude 7000 ft 2133m
Acoustic noise Operating minimum L WAd (bels) 6.5
Airflow (cubic feet per minute
[cfm])
20 cfm minimum 31 cfm maximum
Remote management IBM Integrated Management Module included (user-installable Virtual Media Key available) on a shared Ethernet
connector
*
Maximum measured values were determined with 77°F (25°C) ambient temperature, and your results may va ry.
*
Idle power: Power drawn with the machine(s) logged into the OS, and no other applications running. Memory, HDDs, optical
drives, and tape drives are not being used.
*
Measured maximum power: Maximum measured power is the power drawn by the machine with the CPUs 100-percent used and
memory is used 10 percent more than base usage. The exerciser used is Prime95 (torture test). You can download it at
http://www.mersenne.org.
*
Rated system maximum: The maximum power the machine can draw according to the system label rating.
Table 2. Equipment Approvals and Safety
Equipment Approvals and Safety