Installation guide
2-47
Cisco IGX 8400 Series Installation Guide, Release 9.3.3 and Later Releases
OL-1165-06
Chapter 2 Preparing to Install
Making Power and Ground Connections
Figure 2-32 Pluggable Terminal Block
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use. To see translations of this warning, refer to the Regulatory Compliance and Safety
Information document that accompanied this product.
Step 3 Attach the pluggable terminal block to the receptacle on the PEM.
Step 4 Loop the DC wiring through the strain relief clamp.
Step 5 Connect the DC input wiring to a DC source capable of supplying at least 20 A (typical). The –48 VDC
power source in the building should have a 25-A DC circuit breaker. The building’s wiring should
include an easily accessible disconnect device. Make sure that the ground wire connects to a reliable
building (earth) ground.
10 - 12 AWG
or 4 sq. mm.
48 VDC Return
Safety ground
- 48 VDC