Installation guide

2-41
Cisco IGX 8400 Series Installation Guide, Release 9.3.3 and Later Releases
OL-1165-06
Chapter 2 Preparing to Install
Making Power and Ground Connections
Figure 2-25 IGX 8420 or IGX 8430 AC Connection Wiring
Step 4
Plug the AC power cord into a single-phase wall outlet rated for a nominal voltage.
For an IGX 8410 node, the AC voltage should be from 200 to 240 VAC or 100 to
120 VAC. The outlet must also be capable of supplying up to 12 amperes (A) (13 A in the UK). The
building circuit should be protected with a 15 A or 20 A circuit breaker.
For an IGX 8420 or 8430, the AC voltage should be between 200 and 240 VAC. Each outlet must also
be capable of supplying up to 16 A (13 A in the UK, where the plug has a built-in, 13 A fuse). In
North America, the building circuit should be protected with a 20 A circuit breaker.
Step 5 For the dual power feed version, plug each power cord into a receptacle that connects to a separate
building circuit to provide backup if one building circuit fails. Each building circuit should have a 15 A
or 20 A circuit breaker.
Step 6 The ground (green) wire of the AC power cord is connected to the IGX for safety ground. Make sure that
each AC receptacle in the building is grounded.
Step 7 In addition to the preceding, Cisco recommends that you provide an AC power strip with at least four
outlets. Place the strip near the IGX to supply optional modems, CSUs, DSUs, or test equipment. Be sure
to connect this power strip to an AC source voltage that is standard for the region (for example, 115 VAC
in North America or 230 VAC in Europe).
Note Neither the AC power supplies nor any other components have test points for checking power supply
voltages. For a visual check when power is on, observe whether the AC OK LED and DC OK LED are
lit. Also, use the dsppwr command to check the state of power supplies.
DC Power Connections
A system that uses a DC power source has one or two configurations, as follows:
IGX 8410 node
Single power source
Dual power source (a separate branch circuit supplies each source)
IGX 8420
Single power source
Dual power source (a separate branch circuit supplies each source)
H8397
L2
L1
200 to 240 VAC