Specifications
Installation and Start-up 7-9
Rack Mounting the MGX 8220 Units
Rack Mounting the Modules
Start by mounting the lowest module first and work upwards. In AC system, the lowest module is
the AC power module, in DC systems it is the main cooling module. Use the following steps to
mount the modules.
Step 1 Determine the vertical position in the rack where the shelf or shelves are to be installed.
From this determine the vertical position of the lowest module.
Step 2 Install disposable alignment screws in the upper mounting hole in the rack.
Step 3 Have one person lift the first module into its position and fasten the lower front mounting
screws. (See Figure7-4.)
Step 4 Attach the angle brackets (supplied with the module), one on each side of the mounted
module. Position the brackets so that they can be used to secure the module to the rear rail
of the rack. Holes are provided in the side of the module to accommodate various distances
of the rear rail from the front rail. The angle bracket is attached to the side of the module
using the provided self-tapping screws. (See Figure7-4.) Use the disposable alignment
screws on the rear positioning as well as the front to assure accurate positioning of the first
unit.
Step 5 Attach the angle bracket to the rear rail in the rack using four, number 10-32 machine
screws and flat washers (supplied with the module). The AC Power Module uses a special
bracket at the rear that provides a small shelf for support. (See Figure7-4.) Attach the
bracket to the mounting angle rack using number 10-32 screws. Screws are not mandatory
to hold the bracket to the module.
Step 6 Repeat Step 2 through Step 5 for the remaining modules.
Figure7-4 Using Angle Bracket to Secure Module to Rack