Datasheet
2-3
Cisco 7600 Series Router Installation Guide
OL-4503-24
Chapter 2 Preparing for Installation
Site Requirements
• Never attempt to remove the printed circuit board from the metal carrier.
Caution For safety, periodically check the resistance value of the antistatic strap. The measurement should be 
between 1 and 10 megohm (Mohm).
Environmental Requirements
Insure adequate spacing between racks using the information in Table 2-1. Keep all of the vents clear of 
obstructions, including dust and foreign conductive material, and away from the exhaust ports of other 
equipment. 
Heat dissipation is an important consideration for sizing the air-conditioning requirements for an 
installation. The power and heat associated with a Cisco 7600 series router varies based upon these 
considerations:
• Power supply type
• Module types and quantities
• Average traffic levels
Unless otherwise noted, the information in Table 2-2 through Table 2-18 assumes worst-case conditions 
(with GBICs and port adapters installed, if applicable), so typical numbers are approximately 30 percent 
below the numbers listed here. See Table 2-19 for a sample calculation of a router configuration.
This section provides the power and heat numbers for the Cisco 7600 series chassis and modules. The 
following power requirements and heat dissipation tables are provided:
• Chassis and fan trays—Table 2-2
• Supervisor engines—Table 2-3
• Policy Feature Cards (PFCs)—Table 2-4
• Distributed Forwarding Cards (DFCs)—Table 2-5
Ta b l e 2 - 1 C h a s s i s  A i rfow Requirements
Chassis Model
Airflow 
Intake
Airflow 
Exhaust
Air Filter 
Option
Minimum 
Clearance 
(walls)
Minimum 
Horizontal 
Separation
CISCO7603 (Figure 1-13) Right side Left side No 6 in (15 cm) 12 in (30.5)
CISCO7603-S (Figure 1-14) Right side Left side No 6 in (15 cm) 12 in (30.5)
CISCO7604 (Figure 1-15) Right side Left side
1
1. See Installing the Air Filter Assembly on a Cisco 7606 Router and the Cisco 7606-S Router (Optional), page 5-119.
Yes 6 in (15 cm) 12 in (30.5)
CISCO7606 (Figure 1-16) Right side Left side No 6 in (15 cm) 12 in (30.5)
CISCO7606-S (Figure 1-17) Right side Left side No 6 in (15 cm) 12 in (30.5)
CISCO7609 (Figure 1-18) Front Rear Yes
2
2. See Installing the Air Filter Assembly on a Cisco 7606 Router and the Cisco 7606-S Router (Optional), page 5-119.
6 in (15 cm) 12 in (30.5)
CISCO7609-S (Figure 1-18) Front Rear Yes
2
6 in (15 cm) 12 in (30.5)
CISCO7613 (Figure 1-19) Right side Left side No 6 in (15 cm) 12 in (30.5)