Specifications

5
3 Site Preparation
Check the following:
Site is capable of maintaining an ambient temperature of 32 to 104 degrees Fahrenheit
Site power is available and adequate
Cabling requirements (type, distance)
Rack-mounting requirements (working space, proper airflow)
Site Environment
Warning
This unit is intended for installation in restricted access areas. A restricted access area can be accessed only
through the use of a special tool, lock and key, or other means of security. Statement 1017
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations. Statement 1045
Temperature and Humidity Requirements
Table 1 lists the nominal operating and nonoperating environment requirements. Any measurements that approach the
minimum or maximum of a range indicate a potential problem.
Table 1 Operating and Nonoperating Environments
Power Guidelines
Follow these precautions and recommendations when planning power connections to the Cisco uBR7246VXR router:
Check the power at your site before installation and periodically after installation to ensure that you are receiving clean
power. Install a power conditioner if necessary.
Provide proper grounding.
Make sure that the frame ground is tied to a single building ground.
Use a 6-AWG, copper ground conductor (minimum requirement) when attaching the chassis ground to a headend or other
interior ground system.
Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement 1022
Specification Minimum Maximum
Temperature, ambient operating
Temperature, ambient nonoperating and storage
32˚ F (0˚ C)
-4˚ F (-20˚ C)
104˚ F (40˚ C)
149˚ F (65˚ C)
Humidity, ambient (nonconducting) operating 10% 90%
Humidity, ambient (noncondensing) nonoperating and storage 5% 95%
Altitude, operating and nonoperating –197 ft (–60 m) 13,123 ft (4000 m)
Vibration, operating
5 to 200 Hz, 0.5 g (1 octet/min.)
Vibration, nonoperating 5 to 200 Hz, 1 g (1 octet/min.)
200 to 500 Hz, 2 g (1 octet/min.)