Chapter 4 Configuring the Gigabit Ethernet Ports
Installing, Removing, and Maintaining GBICs
GBIC Cabling Restrictions
You must observe the following fiber-optic cabling restrictions when using
GBICs:
The minimum cabling distance for 1000BASE-SX and 1000BASE-LX/LH
GBICs is 6.5 feet (2 meters).
The maximum cabling distance for each GBIC type is listed in Table 4-2.
When using the 1000BASE-LX/LH GBIC with 62.5-micron diameter MMF,
you must install a mode-conditioning patch cord between the MMF
fiber-optic network and the GBIC. The mode-conditioning patch cord
(CAB-GELX-625 or equivalent) is required to comply with IEEE standards.
See the “Patch Cord” section on page 4-10 for more information.
You must insert a 10-dB inline optical attenuator between the single-mode
fiber-optic network and the receiving port on the 1000BASE-ZX GBIC at
each end of the link if the link length is less than 15.5 miles (25 km).
Table 4-3 GBIC Optical Power Characteristics
Parameter
1000BASE-SX
(WS-G5484)
1000BASE-LX/LH
(WS-G5486)
1000BASE-ZX
(WS-G5487)
Transmitter output power
(min/max)
0/–9.5 dBm –3/–9.5 dBm 0/4.77 dBm
Receiver maximum input
power
0 dBm –3 dBm –3 dBm
Receiver sensitivity –17 dBm –19 dBm –23 dBm
Channel insertion loss
50/125 micron
1
MMF
1. 1 micron (µ) equals 1 micrometer or 10
-6
meters
3.4 dBm 4.4 dBm
62.5/125 micron MMF 3.2 dBm 6 dBm
9/10 micron SMF 6.5 dBm 21.5 dBm