Specifications
1-59
Cisco ONS 15454 Troubleshooting and Maintenance Guide
November 2001
Chapter 1 Alarm Troubleshooting
1.3.84 MANRESET
• Not Alarmed (NA) (Condition)
A user performed a manual system reset meaning a user right-clicked a card and chose Reset. Resets
performed during a software upgrade also prompt the alarm.
1.3.85 MANUAL-REQ
• Not Alarmed (NA) (Condition)
The Manual Switch Request on a Facility/Equipment alarm occurs when a user initiates a manual switch
request on an OC-N card or UPSR path. Clearing the manual switch clears the MANUAL-REQ alarm.
Procedure: Clear the Manual Switch and the MANUAL-REQ Condition on an OC-N Card
Step 1 From network view, click the Circuits tab.
Step 2 Highlight the circuit.
Step 3 Click Edit and click the UPSR tab.
Step 4 From the Switch State menu, highlight Clear.
Step 5 Click Apply and click Close.
1.3.86 MEA
• Critical, Service affecting
The Mismatch Between Entity/Equipment Type and Provisioned Attributes alarm occurs when the
physical card inserted in a slot does not match the card type that is provisioned for that slot in CTC. The
alarm clears when the provisioned card type and the physical card type match.
Procedure: Clear the MEA Alarm on a Cross-Connect or Line Card
Step 1 Physically verify the type of card that sits in the reported slot.
Step 2 Click the Inventory tab to reveal the provisioned card type.
Step 3 Determine which card CTC identifies in the reported slot.
Step 4 If you prefer the card type depicted by CTC, physically insert that type of card (provisioned for that slot).
Step 5 If you prefer the card that physically occupies the slot, put the cursor over the provisioned card in CTC
and right-click to choose Delete Card.
The card that physically occupies the slot reboots, and CTC automatically provisions the card type into
that slot.