Specifications
5-11
Cisco ONS 15216 EDFA2 Operations Guide
78-13908-02
Chapter 5 SNMP MIB Installation and Configuration
Tables and Groups
Use the snmp attribute set local cerent15216EdfaOpSaveConfig perform command to save changes.
cerent15216EdfaPumpCfgEntry Table
The cerent15216EdfaPumpCfgEntry table is used to set or get pump operation mode configuration. The
associated table command displays a settings summary or allows you to set pumps. See Table 5-7 for
variable definitions. The factory default mode of operation for the ONS 15216 EDFA2 is constant gain
temperature compensated. Cisco recommends that users contact Cisco Engineering prior to changing
this mode of operation.
cerent15216EdfaCtmpMaxHystere
sis
Integer (0 to 10) Read-write Amount below
cerent15216EdfaCtmpMax
that the case temperature
must drop before the Ctmp
alarm is cleared in degrees
Celsius.
cerent15216EdfaPowerBusDCVol
tageMin
Integer (0 to 70) Read-write Minimum allowable power
bus DC voltage. The default
minimum power bus voltage
is set at –40 VDC. Valid
entries are between 0 and 70
and are in V times –10. For
example, if the voltage
required is –50 VDC, the
power bus DC voltage is
500.
cerent15216EdfaPowerBusDCVol
tageMax
Integer (0 to 70) Read-write Maximum allowable power
bus DC voltage. The default
maximum power bus
voltage is set at –57 VDC.
Valid entries are between 0
and 70 and are in V times
–10. For example, if the
voltage required is –50
VDC, the power bus DC
voltage is 500.
Table 5-6 cerent15216EdfaCfgGroup Variable Descriptions (continued)
Variable Syntax
Maximum
Access Description