Specifications

Chapter 1 Unpacking and Installing the CSS
If the Product is Damaged
1-6
Content Services Switch Getting Started Guide
78-11766-01
If the Product is Damaged
If any portion of the unit or component is damaged in transit, forward an
immediate request to the delivering carrier to perform an inspection of the product
and to prepare a damage report. Save the container and all packing materials until
the contents are verified.
Concurrently, report the nature and extent of the damage to Customer Service.
Report the problem or deficiency to Customer Service along with the model
number and serial number. Upon receipt of this information, you will be provided
with service instructions, or a Return Material Authorization (RMA) Number and
shipping information.
Installing the CSS 11050 or CSS 11150
The CSS 11050 or CSS 11150 can be placed on a flat surface as a free-standing
unit or rack-mounted in an equipment cabinet. The following sections describe
the steps to install the CSS as a:
Free-standing unit
Rack-mounted unit
Prior to installing the CSS, observe the following installation requirements:
The ambient operating temperature is 32° to 104° F (0 to 40° C).
If you install the CSS in a closed or multi-unit rack, the operating ambient
temperature of the rack environment may be greater than the room ambient
temperature. Ensure that the temperature does not exceed the CSS maximum
ambient operating temperature.
The minimum clearance requirement is 2 inches (10 cm) of air flow space on
both sides of the chassis.
Ensure that the CSS is reliably grounded to earth. We recommend that you do
not use power strips or extension cords to connect the CSS to the power
source.