Cisco Physical Access Gateway User Guide
OL-20932-02
Chapter 1 Overview
Door Device Wiring Requirements
Door Device Wiring Requirements
The wires used for an access control door depend on the devices installed at the door. Before installing
the wiring for an access control system, do the following:
Determine the number and type of door devices used at each door (as shown in Figure 1-6).
Determine the number and type of wires used for each device, based on the descriptions in Table 1-2.
Determine the length of the wires based on the distance between the device and the access control
Gateway, or optional module (such as a Reader, Output or Input module).
Figure 1-6 Air Return Using Ceiling Space or Using Ductwork
Table 1-2 describes the wires used for typical input and output door devices. Refer to the device
documentation for more information and to verify the following requirements.
Table 1-2 Wires Used for Typical Door Devices
Function
# of
Wires
Typical
Wire
Gauge Type Use
Request to Exit 2 22 Input Used to exit the door. This may be replaced by an
egress crash bar if the exit is not alarmed.
Door position
switch
2 22 Input Used to determine if door is open or closed. This
device can cause a door forced open alarm after a
time out. This devise is usually supervised.