Network Device Installation Guide

Send documentation comments to mdsfeedback-doc@cisco.com.
D-12
Cisco MDS 9500 Series Hardware Installation Guide
OL-17467-02
Appendix D Technical Specifications
Power Specifications for the Cisco MDS 9509 Director
16-port 1-Gbps/2-Gbps Fibre
Channel module,
DS-X9016
3.x 210 897 2.92 2.19 1.46 1.09
2.x and
1.x
220 940 3.05 2.29 1.53 1.15
18/4 Multiservice module,
DS-X9304-18K9
3.2.(1) 200 855 2.78 2.08 1.39 1.04
MPS-14/2 module DS-X9302-14K9 3.x 200 854 2.78 2.08 1.39 1.04
2.x and
1.x
227 970 3.15 2.37 1.57 1.19
8-port IPS module
DS-X9308-SMIP
3.x 200 854 2.78 2.08 1.39 1.04
2.x and
1.x
220 940 3.05 2.29 1.53 1.15
4-port IPS module
DS-X9304-SMIP
3.x 160 683 2.22 1.67 1.11 0.83
2.x and
1.x
185 789 2.57 1.93 1.28 0.96
32-port SSM
DS-X9032-SSM
3.x 281 1200 3.90 2.93 1.95 1.46
2.x and
1.x
295 1260 4.10 3.07 2.05 1.54
32-port ASM
DS-X9032-SMV
3.x 281 1200 3.90 2.93 1.95 1.46
2.x and
1.x
295 1260 4.10 3.07 2.05 1.54
CSM
DS-X9560-SMC
3.x 200 854 2.78 2.08 1.39 1.04
2.x and
1.x
210 919 2.99 2.19 1.50 1.12
48-port 8-Gbps switching module,
DS-X9248-96K9
4.x 298 1273 4.14 3.11 2.07 1.55
24-port 8-Gbps switching module,
DS-X9224-96K
4.x 273 1163 3.79 2.84 1.90 1.42
4/44-port 8-Gbps Host-Optimized
switching module,
DS-X9248-48K9
4.x 214 915 2.98 2.23 1.49 1.12
Table D-12 Requirements and Heat Dissipation for 2500-, 3000-, and 4000-W AC Power Supplies (continued)
Module Type/
Product Number
NX-OS
Release
SAN-OS
Release
Power
Required
(watts)
Heat
Dissipation
(BTU/hr)
Input Current
90 VAC
(amps)
120 VAC
(amps)
180 VAC
(amps)
240 VAC
(amps)