Power Specifications for the Cisco MDS 9509 Director
Component Power Requirements and Heat Dissipation for the Cisco MDS 9509
Director
When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power
and heat associated with a Cisco MDS 9509 Director varies based upon the following considerations:
• Power supply type
• Switching module type and number of switching modules installed
• Average switching traffic levels
Table D-12 and Table D-13 list the power requirements and heat dissipation for the components of the
Cisco MDS 9509 Director.
Note Unless noted otherwise, the data listed in Table D-12 and Table D-13 is based on worst-case conditions.
Typical numbers are approximately 30 percent below the numbers listed here.
Ta b l e D-12 Requirements and Heat Dissipation for 2500-, 3000-, and 4000-W AC Power Supplies
Module Type/
Product Number
NX-OS
Release
SAN-OS
Release
Power
Required
(watts)
Heat
Dissipation
(BTU/hr)
Input Current
90 VAC
(amps)
120 VAC
(amps)
180 VAC
(amps)
240 VAC
(amps)
Cisco MDS 9509 chassis with fan
module
DS-C9509
3.x 210 897 2.92 2.19 1.46 1.09
2.x and
1.x
216 920 3.00 2.25 1.50 1.13
Supervisor/fabric 1
DS-X9530-SF1
3.x 210 897 2.92 2.19 1.46 1.09
2.x and
1.x
220 940 3.05 2.29 1.53 1.15
Supervisor-2, DS-X9530-SF2-K9 3.x 126 538 1.75 1.31 0.88 0.66
48-port 4-Gbps switching module,
DS-X9148
3.x 185 790 2.57 1.93 1.28 0.96
2.x and
1.x
— — — — — —
24-port 4-Gbps switching module,
DS-X9124
3.x 147 628 2.04 1.53 1.02 0.77
2.x and
1.x
— — — — — —
12-port 4-Gbps switching module,
DS-X9112
3.x 132 564 1.83 1.38 0.92 0.69
2.x and
1.x
— — — — — —
4-Port 10-Gbps switching module,
DS-X9704
3.x 172 734 2.39 1.79 1.19 0.90
2.x and
1.x
— — — — — —
32-port 1-Gbps/2-Gbps Fibre
Channel module,
DS-X9032
3.x 191 816 .2.65 1.99 1.33 0.99
2.x and
1.x
200 855 2.78 2.08 1.39 1.04