Specifications

C E N T A U R U S P R I M E
1
11
1
Gateway Installation
Basic Information
Summary
his section will help to give a basic overview and quick summary of the
procedures needed to install the Trane-485 Gateway Panel. Detailed
instructions are also provided later in this guide. The Centaurus Prime Trane-
485 Gateway allows any front-end system (Modbus Master or BACnet/IP) that
communicates using the either industry-standard Modbus or BACnet protocols to
communicate to Trane VAV field equipment. The Trane VAV field devices will
appear to the front-end system as a series of Modbus SLAVE devices or BACnet
Devices. Each Trane-485 Controller will map to one of these devices. Real time point
data from the Trane VAV controllers is then mapped to equivalent registers, coils, and
bits on the Modbus system, or as AI, BI, AO, and BO
objects on the BACnet system. All operations are
transparent to the user and the host computer.
Connections to the Trane-485 Gateway are simple and clearly marked. They consist of:
Power Supply, 120 Volts AC (optionally, 220 or 240 Volts AC)
Trane-485 VAV Device trunks (up to four)
Modbus-RTU Network, (RS-485 or IP), or BACnet/IP Network
Local Mode Port for commissioning via Laptop Computer
All Hardware necessary to connect the Gateway to the Trane-485 devices is included
in the 16 X 14” X 8 plastic cabinet that is easily mounted in a convenient location.
The BACnet/IP network is a 10-Mbaud Ethernet, only. The Modbus
RTU Network connects to the Trane-485 Gateway via either (a) a 10-
Mbaud Ethernet, (b) an RS-422 serial link (a four-wire, full-duplex
connection), an RS-485 serial link (a two-wire, half-duplex connection),
or an (c) RS-232 serial link (a three-wire, full-duplex connection). The
RS485 or RS422 connections must be used in a multi-drop network
Chapter
1
I C O N K E Y
Valuable information
T