Specifications

C E N T A U R U S P R I M E
26
2626
26
WCH: (Q)uiet, (1),(2),(3),(4) to watch trunks; (V)erbose, (M)odbus, (X)-it :1
*** TRUNK 1 is now being MONITORED ***
-- SCAN: Trunk #1, TRANE #4 Device # 1 Type: 0
AI 30001 Zone Temperature Counts: 72 = 72.00
AI 30002 Active Heating SP Used Counts: 71 = 71.00
AI 30003 Active Cooling SP Used Counts: 76 = 76.00
AI 30003 Active Cooling SP Used Counts: 76 = 76.00
AO 40004 OCCUPIED Heating SPT Counts: 71 = 71.00
AI 30004 OCC Heating Value Counts: 71 = 71.00
AO 40005 OCCUPIED Cooling SPT Counts: 76 = 76.00
AI 30005 OCC Cooling Value Counts: 76 = 76.00
AO 40006 UNOCCUPIED Heating SPT Counts: 67 = 67.00
AI 30006 UNOCC Heating Value Counts: 67 = 67.00
AO 40007 UNOCCUPIED Cooling SPT Counts: 80 = 80.00
AI 30007 UNOCC Cooling Value Counts: 80 = 80.00
AI 30008 Damper/Valve Pos Counts: 24 = 24.00
AI 30009 Maximum Flow (Size) Counts: 16 = 1100.00
AI 30010 Present CFM Flow Counts: 0 = 0.00
AO 40011 Max Heating Flow SPT Counts: 16 = 16.00
AI 30011 Max Heating Flow Counts: 16 = 16.00
AO 40012 Min Heating Flow SPT Counts: 15 = 15.00
AI 30012 Min Heating Flow Counts: 15 = 15.00
AO 40013 Max Cooling Flow SPT Counts: 90 = 90.00
AI 30013 Max Cooling Flow Counts: 90 = 90.00
AO 40014 Min Cooling Flow SPT Counts: 25 = 25.00
AI 30014 Min Cooling Flow Counts: 90 = 90.00
AO 40015 Fan Ctl Offset SPT Counts: 3 = 3.00
AI 30015 Fan Ctl Offset Value Counts: 3 = 3.00
DI 10001 Current Fan Status Raw Value: 8 ==> OFF
DI 10002 Control Mode Status Raw Value: 0 ==> COOL
DI 10003 Heating Status Raw Value: 8 ==> OFF
DO 10 Damper Force Open CTL Raw Value: 0 ==> NORMAL
...etc…
(V)erbose: When (V) is pressed while in monitor mode, the full protocol data packets
will be displayed as well for each scanned device.
*** Now in VERBOSE MODE (full packets) for monitored trunks
-- SCAN: Trunk #1, TRANE #4 Device # 1 Type: 0
--TO Trunk 1: 00 04 01 00 1C AA 3D
-- Set up TIMEOUT, Trunk #1, to be 6153193, TMO @baud = 100
-FRM Trunk 1: <Incomplete>
TIMEOUT" on Trunk: 1, error count = 0
--TO Trunk 1: 00 04 01 00 1C AA 3D
--FRM Trunk 1:00 84 01 00 1C 08 00 11 01 1C 00 00 00 18 00 19 47 4C
47 4C
19 5A 0F 03 43 50 00 00 10 40 AA AA 3D 85 0F <Valid>
AI 30001 Zone Temperature Counts: 72 = 72.00
AI 30002 Active Heating SP Used Counts: 71 = 71.00
AI 30003 Active Cooling SP Used Counts: 76 = 76.00