Specifications

C E N T A U R U S P R I M E
24
2424
24
(P)riority: (BACnet ONLY) Use this to select the priority that you will issue
subsequent control and release operations at.
CTL: (S)elect, (P)riority, (C)ontrol, (R)elease, (D)etail, (X)-it :P
PRI: Enter a PRIORITY to do your controls at (1 to 16): 4
Control and Release Operations will now be done at Priority 4.
(C)ontrol: (BACnet version) This option will let you control the selected point, at
whatever priority level you are currently at.
CTL: (S)elect, (P)riority, (C)ontrol, (R)elease, (D)etail, (X)-it :C
CTL: You may enter a new value to set the selected object to.
Enter a field value (0 or 1 for digitals; valid number for analogs) : 70
The new value of the object will be : 0
Adding to Control Queue, at #2. Device #6, AO #114
Queued Control; Trunk #1, Device #6, AO #114 -- to: 70.000 pri = 4
(R)elease: This option will let you release control for the selected point at your selected
priority level (valid for the BACnet variant of the Gateway, only!):
CTL: (S)elect, (P)riority, (C)ontrol, (R)elease, (D)etail, (X)-it :R
RLS: Are you sure that you want to RELEASE this object?
ARE YOU SURE? If so, enter Y for Yes, and then the ENTER key.
(or any other keys if you do NOT want to RELEASE the object) : Y
The object AO #114 has been released from Priority #4.
(D)etail: will display details associated with the selected point.. Let’s first look at a
Modbus version of an object’s detail:
CTL: (S)elect, (P)riority, (C)ontrol, (R)elease, (D)etail, (X)-it :D
MB Address: 30001, Type = AI, "Zone Temperature"
Field Unit / Subunit : 4 / 0 Field Address :30001
Object Flags (bits) : 0 Error Counter :0