TagID: "VAV #4, TRUNK 1 (MB #1)" statistics:
Packets Today: 463
RX Errors Today: 0 % Error: 0.000
TX Errors Today: 4 % Error: 0.864
Last Comm at: 17:13:26 on Dec 28, 2002
Point Menu Options
The Point” menu has three options, Select, All, and Detail.
PNT: (S)elect, (A)ll, (D)etail, (X)-it :
(A)ll: This will display all points and their current values for the targeted device. What
follows below is an example from a Modbus gateway. A BACnet gateway will display
the BACnet object type and Instance number in the first part of each line, rather than
the Modbus register number). Data is the same for both gateway “flavors”, it is just
the object mapping which is different in the two protocol systems (register addresses
versus object type/instances).
PNT: (S)elect, (A)ll, (D)etail, (X)-it :A
DEVICE #1 is field device/subdevice/type 4/0/1
TagID: "VAV #4, TRUNK 1 (MB #1)", has 54 objects under it, 1st one at: 54
MB Reg 30001 (AI) "Zone Temperature " Fld: 72 ==> 72.00
MB Reg 30002 (AI) "Active Heating SPT Used " Fld: 71 ==> 71.00
MB Reg 30003 (AI) "Active Cooling SPT Used " Fld: 76 ==> 76.00
MB Reg 30004 (AI) "Occupied Heating SPT Val" Fld: 71 ==> 71.00
MB Reg 30005 (AI) "Occupied Cooling SPT Val" Fld: 76 ==> 76.00
MB Reg 30006 (AI) "UnOccupied Heat SPT Val" Fld: 67 ==> 67.00
MB Reg 30007 (AI) "UnOccupied Cool SPT Val" Fld: 80 ==> 80.00
MB Reg 30008 (AI) "Damper/Valve Pos " Fld: 24 ==> 24.00
MB Reg 30009 (AI) "Maximum Flow Size " Fld: 16 ==> 1100.00
MB Reg 30010 (AI) "Present CFM Flow " Fld: 0 ==> 0.00
MB Reg 30011 (AI) "Max Heating Flow " Fld: 16 ==> 16.00
MB Reg 30012 (AI) Min Heating Flow " Fld: 15 ==> 15.00
MB Reg 30013 (AI) "Max Cooling Flow " Fld: 90 ==> 90.00
MB Reg 30014 (AI) "Min Cooling Flow " Fld: 90 ==> 90.00
MB Reg 30015 (AI) "Fan Ctl Offset Value " Fld: 90 ==> 90.00
MB Reg 30016 (AI) "AUX Temperature " Fld: 74 ==> 74.00
MB Reg 10001 (DI) "Current Fan Status " Fld: 0 OFF (0-state)
MB Reg 10002 (DI) "Control Mode Status " Fld: 0 COOL (0-state)
MB Reg 10003 (DI) "Heating Status " Fld: 0 OFF (0-state)
MB Reg 10010 (DI) "Damper Forced Open " Fld: 0 NORMAL (0-state)