Specifications
C E N T A U R U S P R I M E
16
1616
16
TagID: "VAV#4, TRUNK 1 (MB #1)" is ON-LINE & RELIABLE
TagID: "VAV #1, TRUNK 2 (MB #61)" is OFF-LINE! <MUST INIT> (SlowScan)
TagID: "VAV #4, TRUNK 3 (MB #121)" is ON-LINE & RELIABLE
TagID: "VAV #5, TRUNK 3 (MB #122)" is ON-LINE & RELIABLE
TagID: "VAV #6, TRUNK 3 (MB #123)" is ON-LINE & RELIABLE
(A)larms: Not available with Modbus (does not support alarm states). With BACnet,
this does have meaning, but only for points that have alarm states or limits (intrinsic
alarms) defined. At the present time, the Centaurus Prime gateways do NOT support
BACnet alarming, either “intrinsic” or “algorithmic”.
(C)ontrolled: This command will display all controlled points for all Modbus or
BACnet devices.
SUM: (D)evices, (A)larms, (C)ontrolled, (U)nreliable, (X)-it :C
DEVICE #1 is field device/subdevice/type 4/0/1
*** Gateway has NO controls to do! ***
DEVICE #61 is field device/subdevice/type 4/0/1
*** Gateway has NO controls to do! ***
DEVICE #121 is field device/subdevice/type 4/0/1
*** Gateway has NO controls to do! ***
DEVICE #122 is field device/subdevice/type 5/0/0
*** Gateway has NO controls to do! ***
DEVICE #123 is field device/subdevice/type 6/0/0
*** Gateway has NO controls to do! ***
(U)nreliable: This will display all unreliable points for all devices.
SUM: (D)evices, (A)larms, (C)ontrolled, (U)nreliable, (X)-it :U
DEVICE #1 is field device/subdevice/type 4/0/1
*** "PO #7 Action" is UNRELIABLE
*** "PO #6 Action" is UNRELIABLE
*** "COOLING Control" is UNRELIABLE
*** "HEATING Control" is UNRELIABLE
“Devices” Menu Options
The Devices menu is used to display all of the configured devices (A) or to “target” a
specific device and get data about it.