User Manual
Copyright © Cirrus Logic, Inc. 2008
(All Rights Reserved)
http://www.cirrus.com
CS5463: Determining No-load Condition Without
Violating Starting Condition Standards
1. INTRODUCTION
When the CS5463 is used in power meter applications, some customers use the I
RMS
residual value as the
threshold for the exte rnal microprocesso r to decide if the meter is under th e no-load condition, and then find
the meter can not pass the starting test. This applications note gives the reason and the correct solution.
2. NO-LOAD AND STARTING CONDITIONS
According to the standa rd IEC 62053 -22, the definitio n of a no-load condition is defined a s: "When the vo lt-
age is applied with no current flowing in the current circuit, the test output of the meter shall not produce
more than one pulse.". The test of starting condition is defined as: "The meter shall start and continue to
register at 0.001In and unity power factor.".
To meet these requireme nts, a power meter has to use th e correct no-load threshold in order to restrain the
pulse output and energy accumulation when there is no load current but resume pulse output and energy
accumulation when the load is above the starting current (I
st
).
3. DETERMINING A NO-LOAD CONDITION CORRECTLY
The CS5463 has three ene rgy pu lse outp uts (E1, E2, an d E3). T he p ulse outputs un der no-loa d o r starting
condition has been well manipulated by the CS5463. In addition, the CS5463 has a no-load threshold reg-
ister (LOAD
Min
) to help disable the active energy pulse output under some specified condition. When the
magnitude of the P
Active
register is less than LOAD
Min
, the active energy pulse output is disabled.
Different from the energy pulses, the energy register, either mechanical or electronic, is normally manipu-
lated by a microcontroller. T he microcontroller need s to use a variable and a th reshold value to decide if the
meter is under a no-load condition, in which case the values in the power registers should be discarded.
There are two options to select the variable and the threshold.
Table 1: Variable & Threshold Values Comparison
Because I
RMS
exhibits much more system noise than P
Active
, I
RMS
should not be used as a variable
to determine the no-load condition.
Variable
Used
Threshold Value
Com pare
Result
I
RMS
R es idu a l v a lu e (AC of fset ) w ith
inputs of U
n
an d no c u rre nt
BAD
P
Active
Less than the valu e with inputs of U
n
and starting current
GOOD
AN337
DEC '08
AN337REV1