Instructions

Table 3:LINK LED, colour codes�
LINK LED
Colour Status
Flashing red Device not linked
Steady green Device linked
COMS LED: Flashes with each transmission made by the RS-485 port.
4.3.- OPTICAL COMMUNICATIONS PORT
The device has an optical serial communications port on its right side, in accordance with the
UNE EN 62056-21:2003 standard, in order to communicate with other devices in the CEM
family.
4.4- RS-485 COMMUNICATIONS
4�4�1�- MODBUS PROTOCOL
The MODBUS protocol is a communication standard in the industry that enables the network
connection of multiple devices, where there is a master and multiple slaves. Within the
MODBUS protocol the CEM M-RS485 uses the RTU (Remote Terminal Unit) mode.
In RTU mode, message starts and ends are detected with silences of at least 3.5 characters,
and the 16-bit CRC error-detection method is used.
The MODBUS functions implemented in the device are:
Functions 03 and 04. Reading logs.
Function 10. Writing multiple logs.
Due to the communication time between the CEM M-485 and the measurement
module, the minimum time between questions, to different devices connected to
the same bus, should not be less than 250 ms.
4�4�2�- READ COMMANDS
The CEM M-RS485 supports integer type read functions: 0x03 and 0x04.
The device's Modbus variables are specied in Table 4.
Example: Reading of the device's serial number with peripheral number 01.
We will send the following Modbus frame:
Address Function Initial log Log no� CRC
01 04 2710 0002 CRC
The device will respond to us with the next frame:
12
CEM M-RS485