2.3 Modbus RTU
NexSens iSIC data loggers support Modbus RTU sensors connected to a data logger via RS232 or
RS485.
Implementation:
RS232 and RS485, baud rates 1200 to 57600 supported.
Addresses from 1 to 247 are supported.
Registers 0 to 65535 are supported. The software assumes each parameter is in
sequential register order. When registers are not in sequential order, the modbus device
can be added as multiple sensors.
Commands 0x03 for reading holding registers and 0x04 for reading input registers are
supported.
User specified timeout available.
Data types of 2-byte Integer, 4-byte Integer (big-endian), 4-byte IEEE Float (big-
endian), 4-byte Integer (little-endian), and 4-byte IEEE Float (little-endian) are available.