Instruction Manual

Copyright © 2006 CiDRA Corporation Page 9-21
20675-01 Rev 02
Table 14 Transmitter Menu Tree Software Release 03.03.XX (page 6)
Level 1 Level 2 Level 3 Range Description
Line 1
Blank, GVF, SOS, Flow
Rate, Totalizer, Flow
Rate %
Parameter displayed on
line 1
Line 2
Blank, GVF, SOS, Flow
Rate, Totalizer, Flow
Rate %
Parameter displayed on
line 2
Display
Contrast 0 to 1024 (default 170) Contrast of display
Sensor Setup State On/off
Enable / disable each
sensor
Volume
gal, l, m
3
, user, ft
3
, igal,
ft, m
Flow units
Time d, h, m, s, user Time units
User Vol Label User defined
Custom flow volume
label
Use Vol Base gal, l, m
3
, ft
3
, igal, ft, m
Base units for custom
volume label
User Vol Scale
0.0000 e-38 to
9.9999 e+38
Scale factor on custom
volume base
User Time
Label
User defined Custom time label
User Time
Base
d, h, m, s
Base units for custom
time label
Flow Units
User Time
Scale
0.0000 e-38 to
9.9999 e+38
Scale factor on custom
time base
SOS Units Units ft/sec, m/sec Sound speed units
Low End
0% to 100% (3 to 30
ft/s)
Under this value ‘<min
flow’ will be displayed
Flow Cutoff
Range
High End
0% to 100% (3 to 30
ft/s)
Over this value ‘>max
flow’ will be displayed
Units gal, l, m
3
, ft
3
, user def Units for totalizer
Lowcut Enable Enable, Disable
Turns totalizer lowcut
on / off
Lowcut
0% to 100% (3 to 30
ft/s)
Flow values below this
will not be used for
totalizer
Multiplier M, k, 1 Total Multiplier
Reset Reset totalizer value
Totalizer
Input Vol Flow Totalized flow basis
Customize
Wr Protect
Mode
Enable, Disable
When enabled no other
parameters can be
changed