Owner's manual
1.2.2 Serial Communications Settings
1.2.2.1 Configuration
• RS-232
• RS-485 (Default)
1.2.2.2 Data Bits
• 7 bits
• 8 bits (Default)
The Data Bits setting should match the Transmission Mode as
follows. The ability to set the Data Bits independent of
Transmission Mode is to allow for maximum flexibility.
• RTU 8 Data Bits
• ASCII 7 Data Bits
1.2.2.3 Parity
• EVEN (Default)
• ODD
• NONE
1.2.2.4 Stop Bits
• 1 (Default)
• 2
1.2.2.5 Baud Rate
• 2400
• 9600 (Default)
• 19200
• 38400
• 57600
• 115200
Note: The Modbus specification requires the use of 2 Stop Bits when
No Parity is selected.