Owner's manual

9-01 Rev 02 Page 3-28
Table 5 Modbus Holding Registers (continued)
Address Size Type Value Description Values
4563 2 Long
AGC_PERCENT_TH
RESHOLD_LOW
Represents the percentage value of Low Threshold
faults req
uired to be detected before asserting an
Insufficient Gain condition during AGC functions.
4565 2 Long
AGC_SAMPLE_WIN
DO
W
Represents the time window in seconds during which
AGC High and Low Threshol
d faults will be counted.
This is a sliding time window when used during Auto
Gain Adjust functions and a One-Shot time window
during Gain Test functions.
4567 2 Long AGC_RUN_MODE
For future use only. This parameter will be used to
spe
cify if the AGC functions should be executed in a
Continuous mode, or in Single Execution mode.
5001 2 Float Pressure Input External pressure measurement input.
No write control required on these
inputs, ju
st write to them.
5003 2 Float Temperature Input External temperature measurement input.
No write control required on these
inputs, ju
st write to them.
5005 2 Float External Input 1 External Input 1.
No write control required on these
inputs, ju
st write to them.
5007 2 Float External Input 2 External Input 2.
No write control required on these
inputs, ju
st write to them.
5009 2 Float External Input 3 External Input 3.
No write control required on these
inputs, ju
st write to them.
5501 32 Short
Softing Firmware
Rev
Firmware revision of the Softing board.
5533 32 Short PD Tag Fieldbus PD Tag.
5565 32 Short Device ID Fieldbus Device ID.
5597 1 Short Node Address Fieldbus Node Address.
5598 1 Short RB Block Mode Fieldbus Resource Block Mode.
5599 1 Short TB Block Mode Fieldbus Transducer Block Mode.