Section 7—Calibration
Calibration offset offsets the displayed value. Usually, this option is 
used to match displays of two different instruments that are mea-
suring the same temperature, but are displaying different tempera-
tures due to different thermocouple accuracy or placement of the 
thermocouples. Caution is advised when adding an offset to the 
display, since the actual sensed temperature will not be displayed. 
Calibration offset (coFF) is available in the configuration mode, but 
only displays if the security lock (LocH) is set to 736. 
Calibration
19
Section 7–Calibration
Factory Default 
Recovery
This option allow you to return the controller’s configuration param-
eters back to the factory default values (except for the LocH menu). 
This parameter could be used when moving a unit from one applica-
tion to another to give the operator an easy place to begin setup of 
the unit.
Factory Default Recovery is performed in the Configuration Mode, 
menu dFLt. The security lock (LocH) must be set to 736 to perform 
a factory default recovery. 
To reestablish the factory default values:
1.  Disconnect load power.
2.  In the Configuration Mode, set security level (LocH) to 736.
3.  Go to menu dFLt and press  . The controller will automatically 
reset the values. When the display cycles from rEdy to donE, the 
recovery is complete. 
Calibration Offset
The Chromalox 2110 Temperature Controller is factory calibrated 
before shipment. Recalibration is not needed when you receive 
and install the product. Periodic calibration checks or adjustments 
should not be necessary under normal operating conditions. Chro-
malox recommends you recalibrate the controller if all instruments in 
your facility are periodically calibrated to a known standard.
The 2110 always retains the original factory calibration values for 
the J, K, and RTD inputs. In an application, only one of these sensor 
inputs will be used. The 2110 only can retain manual calibration for a 
single sensor. 