Section 4–Adjusting Set Point and Configuration
Configuration
Menus
continued
For calibration menus (CoFF, dFLt, & CALS), see Section 7–
Calibration
Menu
Code Function
Adjustable
Range
Factory
Default
Security
Level
CYCL
Cycle Time
The time for the output to
complete ON to OFF to
ON cycle. Used only with
proportional control. A fast
cycle time provides better
control, but can cause
premature wear to contactor or
other power switching devices.
Magnetic contactors should not
be switched at less than a 30
second cycle time. This menu
is active when the dip switch is
set to “PI”.
.1 to 60.0
Sec.
Output
R1, R3 =
30 sec.
S0, S1,
S2, V0 =
1 sec.
B
db
On/Off Dead Band
The range above/below set
point in which no control action
takes place. Determines at
what temperature the output
switches ON and OFF. For a 5°F
dead band, 2.5°F is above and
below the set point. This menu
is active when the dip switch is
set to “ONOF”.
1 to 100 °F
or °C
5 Foc
B
ALty
Alarm Type
Select high or low alarm.
Off, Hi or Lo OFF B
ALSP
Alarm Set Point
Temperature level that will
actuate the alarm.
0 to 100 °F
or °C
5 B
ALdb
Alarm Dead Band
Difference of temperature from
alarm set point before an active
alarm resets.
0 to 100 °F
or °C
5 B
SPLL
Set Point Lower Limit
Lower limit to which set point
may be set without security
code access.
Sensor
Range
°F or °C
Span
Low
B
SPUL
Set Point Upper Limit
Upper limit to which set point
may be set without security
code access. This prevents
an operator from setting the
set point temperature to a
level which would damage
equipment or process.
Sensor
Range
°F or °C
Span
High
B
outl
Output Limit
Limits the percentage of
output that can be applied in
proportional control.
0 to 100% 100 B