User manual

Chromalox 2110
Security Codes and
Levels
To limit access to the user configuration interface, security codes
are assigned to different menu levels. Make security codes avail-
able to operators, maintenance crew, supervisors, etc. according
to what function level you want for each group. Security Level C
is not recommended for most users. Gain access to configura-
tion menus using the following codes.
Security Level Security Code Function
A All Values Allows adjustment of
the Set Point
B 458 Basic menus
C 736 Calibration menus
Configuration
Menus
The following configuration menus can be accessed through the
user interface (see Configuration, page 12).
14
Section 4–Adjusting Set Point and Configuration
Menu
Code Function
Adjustable
Range
Factory
Default
Security
Level
Loch
Security Lock
0-999 458
A
Proc
Process Variable Display
Displays the actual process
temperature.
Read Only
°F or °C
N/A
A
SP
Process Set Point Adjust
Adjusts the target process
temperature.
Sensor
Range
°F or °C
0°F A
Pb
Proportional Band
Temperature range above/below
set point where proportional
control is active. Most
applications require a band
between 10 to 200°F. This menu
is active only when the dip
switch is set to “PI”
1 to Sensor
Span
Maximum
°F or °C
25 B
ArSt
Automatic Reset
Control feature that
automatically corrects for small
temperature offsets that occur
in proportional control. The
higher the setting, the faster the
correction occurs. A high setting
could cause overshoot during
start-up. A low setting will not
allow process temperature
to reach to set point quickly
enough. A setting of “0” turns
off automatic reset. This menu
is active only when the dip
switch is set to “PI”.
0.0 to 100.0
Repeats/
Min.
0.1