5.13 “Soft Start” FUNCTION5.13 “Soft Start” FUNCTION
5.13 “Soft Start” FUNCTION5.13 “Soft Start” FUNCTION
5.13 “Soft Start” FUNCTION
At power up, the instrument will measure the
process variable and compare the measured value
with a programmed threshold (see P10 parameter
in chapter 4).
If the measured value is lower than the pro-
grammed value, the instrument will limit the
maximum output power (see OLH operative
parameter) for a programmed time (see tOL
operative parameter).
If tOL is equal to InF, the limiter is ever active.
6.6.
6.6.
6.
ERROR MESSAGESERROR MESSAGES
ERROR MESSAGESERROR MESSAGES
ERROR MESSAGES
6.16.1
6.16.1
6.1
MEASUREMENT ANOMALY SIGNALMEASUREMENT ANOMALY SIGNAL
MEASUREMENT ANOMALY SIGNALMEASUREMENT ANOMALY SIGNAL
MEASUREMENT ANOMALY SIGNAL
The instrument display (the upper display for model
1603E) shows the OVERRANGE and UNDERRANGE
conditions with the following indications:
Overrange Underrange
The example shows the display of model 1603E.
Model 1601E displays 4 digits.
The sensor break can be signalled as:
- for TC/mV input : OVERRANGE or
UNDERRANGE selected by
a solder jumper
- for RTD input : OVERRANGE
On RTD input, a special test is provided to signal
OVERRANGE when input resistance is less than 15
ohm (Short circuit sensor detection).
NOTENOTE
NOTENOTE
NOTE:
When:
- The instrument is set for one control out only and
an OVERRANGE is detected, the OUT 1 turns
OFF (if reverse action) or ON (if direct action).
- The instrument is set to use two control outs and
an OVERRANGE is detected, OUT 1 turns OFF
and OUT 2 turns ON.
- The instrument is set for one control out only and
an UNDERRANGE is detected, the OUT 1 turns
ON (if reverse action) or OFF (if direct action).