User`s manual
22
GBGB
GBGB
GB
Timer mode 4 [P22= 8]Timer mode 4 [P22= 8]
Timer mode 4 [P22= 8]Timer mode 4 [P22= 8]
Timer mode 4 [P22= 8]
The instrument operates using SP set point and
the timer is normally reset.
When the instrument detects the transfer from
contact open to close it selects SP2 as operative
set point and starts the time count down.
When the time count is equal to 0 the instrument
comes back to the SP set point.
1603E display management1603E display management
1603E display management1603E display management
1603E display management: when the
instrument starts the time count down, the upper
display shows the measured value while the lower
display shows time count down.
1601E display management1601E display management
1601E display management1601E display management
1601E display management: when the
instrument starts the time count down, the display
shows the time count down.
Pushing pushbutton it is possible to display the
measured value.
NOTENOTE
NOTENOTE
NOTE: for both instruments, when the time is
finished the instrument comes back to the normal
display mode.
ClosedOpen
SP2
SP
Open Open
Time
Logic input
Timer mode 5 [P22 = 9]Timer mode 5 [P22 = 9]
Timer mode 5 [P22 = 9]Timer mode 5 [P22 = 9]
Timer mode 5 [P22 = 9]
The instrument start in "Power OFF" mode and it
remains in "Power OFF" mode until the contact is
closed.
When the contact has been opened the instrument
starts the control using SP set point and starts the
time count down.
When the time count is equal to 0 the instrument
comes back to the "Power OFF" mode and the
output 2 will be energized.
The Out 2 reset will be made when the logic input
will be closed.
1603E display management1603E display management
1603E display management1603E display management
1603E display management: when the
instrument starts the time count down, the upper
display shows the measured value while the lower
display shows time count down.
1601E display management1601E display management
1601E display management1601E display management
1601E display management: when the
instrument starts the time count down, the display
shows the time count down.
Pushing pushbutton, it is possible to display the
measured value.
NOTENOTE
NOTENOTE
NOTE: for both instruments, when the time is
finished the instrument comes back to the usual
display of the Power OFF mode.
SP
Time
Output 2
OFF
OFF ON OFF
Contact
Closed Open Open
Closed
Stop Run Stop Run Stop Run
Output
Power
OFF
Output
Power
OFF
1601-03-1-CX.pmd 13/01/2004, 10.4322