User`s manual
16
GBGB
GBGB
GB
3) The limits of the proportional band settable by
the SMART function are programmed by
parameters P16, P17 and P18 .
4) The lower limit of the integral time settable by
the SMART function is programmed by
parameter P20 .
5) When ON/OFF control is programmed (Pb=0),
the SMART function is disabled.
6) SMART enabling/disabling can be protected by
the safety lock (see parameter P15).
5.45.4
5.45.4
5.4
MANUAL RESET OF THE ALARMMANUAL RESET OF THE ALARM
MANUAL RESET OF THE ALARMMANUAL RESET OF THE ALARM
MANUAL RESET OF THE ALARM
If the alarm has been configured as a latched
alarm, the alarm status persists even after the
alarm condition disappears.
To reset the alarm, press the FUNC pushbutton to
select the parameter “
n.rSn.rS
n.rSn.rS
n.rS” (the display will show
“
n.rSn.rS
n.rSn.rS
n.rS” and “
OFFOFF
OFFOFF
OFF”. Use the and pushbuttons
to select “
ONON
ONON
ON” and press the FUNC pushbutton.
The alarm reset action will only be successful if the
alarm condition has disappeared.
5.55.5
5.55.5
5.5
SMART ALGORITHMSMART ALGORITHM
SMART ALGORITHMSMART ALGORITHM
SMART ALGORITHM
This function gives best process control.
To enable the SMART function, press the SMT
pushbutton for more than 1.5 s, when the
instrument is in normal display mode. The SMT
LED will be lit continuously or flash according to
the algorithm automatically selected.
When the SMART function is enabled, the
traditional control parameters (
PBPB
PBPB
PB
, ,
, ,
,
TITI
TITI
TI
, ,
, ,
,
TDTD
TDTD
TD and
rCrC
rCrC
rC) can be displayed but not modified.
When the traditional control (PID) is desired, press
the SMT pushbutton again (for more than 1.5 s) to
turn the "SMART" OFF. The instrument maintains
the actual control parameters setting and allows
parameter modification.
NOTESNOTES
NOTESNOTES
NOTES:
1) During operation of the SMART function, the
relative cooling gain (if controlled by SMART) is
limited within the following ranges:
Cooling medium Span
Air 0.85 to 1.00
OIL 0.80 to 0.90
H
2
O 0.30 to 0.60
2) The SMART function uses a derivative time equal
to 1/4 of the integral time.
5.65.6
5.65.6
5.6
INHIBITION OF THE OUT SIGNALINHIBITION OF THE OUT SIGNAL
INHIBITION OF THE OUT SIGNALINHIBITION OF THE OUT SIGNAL
INHIBITION OF THE OUT SIGNAL
This feature manually turn OFF the control output.
To turn the out signal OFF, press the
pushbutton first and then press the FUNC
pushbutton.
Keeping them both pressed for more than 3
seconds.
The instrument will display “
OFFOFF
OFFOFF
OFF” instead of
indicating the set point; the out signal will switch
OFF and the instrument will work as a simple
indicator.
When the control outs are disabled, the alarms are
also disabled and forced to the no-alarm condition.
The modification of the control parameters is still
enabled.
To return to normal control, press the pushbutton
first and then press the FUNC pushbutton.
Keeping them both pressed for more than
3 seconds, the instrument returns to normal display
mode.
NOTES NOTES
NOTES NOTES
NOTES :
1) If the out is turned OFF when the SMART
function is performing the first part of the SMT
algorithm (LED SMT flashing), the SMART
function will be aborted and when the
instrument comes back to the normal control,
the SMART function will be disabled.