NOTE: The alarm stand-by function disables the
alarm indication at instrument start up and after a
set point modification until the process variable
reaches the alarm threshold.
P26 = treshould of the guarantee soakP26 = treshould of the guarantee soak
P26 = treshould of the guarantee soakP26 = treshould of the guarantee soak
P26 = treshould of the guarantee soak
functionfunction
functionfunction
function
P26 is available when P22 is greater than 2.
This function stop automatically the time count
down when the measured value is out of the band
defined by the set point plus and minus P26 value.
- When P1 = 5 : P26 is programmable from 0.1 to
50.0 eng. units.
- When P1 ≠ 5 : P26 is programmable from 1 to
500 eng. units.
Above max value the display shows “OFF” and this
finction is disabled.
The configuration procedure is completed and the
instrument shows "
CnFCnF
CnFCnF
CnF" on the display.
To quit the configuration, press SMT and FUNC
simultaneously (press first SMT and immediately
afterwards FUNC) keeping both the pushbuttons
pressed for three seconds.
5.5.
5.5.
5.
OPERATOR MODEOPERATOR MODE
OPERATOR MODEOPERATOR MODE
OPERATOR MODE
The display and modification of the operator
parameters can be protected by a secret code.
For more information see section 4.2.
5.15.1
5.15.1
5.1
PRELIMINARY COMMENTSPRELIMINARY COMMENTS
PRELIMINARY COMMENTSPRELIMINARY COMMENTS
PRELIMINARY COMMENTS
It is assumed, at this point, that the instrument has
been correctly configured as indicated in
Section 4.
- Model 1603E displays the value measured on
the upper display: the lower display is normally
used to display the operating set point (below
this condition is defined as “Normal display”).
- Model 1601E displays the value measured
(below this condition is defined as “Normal
display”) or, alternatively, the operating set point
(in this case the SP led lights up).
To change from the display of the set point to
that of the value measured, or vice versa, press
pushbutton .
All the parameters can be displayed sequentially by
pressing the FUNC pushbutton.
- Model 1603E displays the abbreviated name of
the parameter selected on the lower display, on
the upper display the value set.
- Model 1601E displays alternatively the name of
the parameter and its value: during the
modification it displays only the value.
To modify the setting of a parameter proceed as
follows:
1) By means of the FUNC pushbutton select the
parameter to be modified.
2) Using the and keys set the value
required.
1601-03-1-CX.pmd 13/01/2004, 10.4314