User`s manual

7
GBGB
GBGB
GB
code and the numerical value alternatively.
To alter the value set press or and confirm
with FUNC.
The parameter for loading the default parameters
is shown in section B at the end of the manual.
4.44.4
4.44.4
4.4
CONFIGURATION PARAMETERSCONFIGURATION PARAMETERS
CONFIGURATION PARAMETERSCONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
P1 - Type of input and standard rangeP1 - Type of input and standard range
P1 - Type of input and standard rangeP1 - Type of input and standard range
P1 - Type of input and standard range
Type of input Range
0 TC type L 0 / +900 °C
1 TC type J 0 / +999 °C
(1603E)
0 / +1000 °C
(1601E)
2 TC type K 0 / +999 °C
(1603E)
0 / +1370
(1601E)
3 TC type N 0 / +999 °C
(1603E)
0 / +1400 °C
(1601E)
4 RTD type Pt 100 -199 / +800 °C
(1603E)
-200 / +800 °C
(1601E)
5 RTD type Pt 100 -19.9 / +99.9 °C
(1603E)
-199.9 / +400.0 °C
(1601E)
6 TC type T 0 / +400 °C
8 TC type L 0 / 999 °F
(1603E)
0 / 1652 °F
(1601E)
9 TC type J 0 / 999 °F
(1603E)
0 / 1832 °F
(1601E)
10 TC type K 0 / 999 °F
(1603E)
0 / 2498 °F
(1601E)
11 TC type N 0 / 999 °F
(1603E)
0 / 2552 °F
(1601E)
12 RTD type Pt 100 -199 / 999 °F
(1603E)
-328 / 1472 °F
(1601E)
13 TC type T 0 / 752 °F
NOTE:NOTE:
NOTE:NOTE:
NOTE: On the instrument front panel two leds
indicate the setting of the temperature in °C or °F,
depending on the configuration.
If the modification of the parameters has been
enabled, the passage in configuration is free.
If not it will be allowed by entering, when
requested, the numerical value programmed in
P11, or code 408.
P11 = 500/999P11 = 500/999
P11 = 500/999P11 = 500/999
P11 = 500/999 As for the previous point, with the
difference that AL (alarm threshold) can be
modified as well as SP, SP2 and T.
In the two previous cases, with P14 = On the
parameters set as not modifiable can however be
displayed. With P14 = OFF they are not.
4.34.3
4.34.3
4.3
ACCESS TO THE CONFIGURATIONACCESS TO THE CONFIGURATION
ACCESS TO THE CONFIGURATIONACCESS TO THE CONFIGURATION
ACCESS TO THE CONFIGURATION
PROCEDUREPROCEDURE
PROCEDUREPROCEDURE
PROCEDURE
To access the configuration, press SMT and
FUNC simultaneously (press first SMT and
immediately afterwards FUNC) keeping both the
pushbuttons pressed for three seconds.
In the model 1603E the lower display will show
CnfCnf
CnfCnf
Cnf, the upper
OFFOFF
OFFOFF
OFF. In model 1601E
OFFOFF
OFFOFF
OFF and
CnFCnF
CnFCnF
CnF will appear alternatively.
Press or within 10 seconds to set
ONON
ONON
ON, then
confirm with FUNC.
If the device is in the protected condition (see
previous section), the lower display (1603E)
shows Cnf, the upper a dashed line (instead of
OFFOFF
OFFOFF
OFF). In model 1601E the two wordings appear
alternately.
By means or enter the value entered in P11, or
value 408. Press FUNC to confirm.
The instrument is now in configuration mode, and
the display shows
CnfCnf
CnfCnf
Cnf steadily for both models.
Via FUNC we advance to the first parameters.
In configuration, the lower display shows the
code of the parameter (P1-P21), the upper the
numerical value or the selection code.
In the
model 1601E, the display shows the parameter
1601-03-1-CX.pmd 13/01/2004, 10.427