User manual
Universal User Manual  5   V1.4 September 2012 
www.chroma
-
q.com
Detail of connector wiring 
The correct wiring between male & female connectors is 'one to one'. 
Pin #  Pin #  Minimum Cable size 
1  Ground (-ve)  2.50mm² (14 AWG) 
2  Control data minus (-)  0.35mm² (22 AWG) 
3  Control data plus (+)  0.35mm² (22 AWG) 
4  24V DC (+ve)  2.50mm² (14 AWG) 
Chassis  Cable shield/drain wire  0.25mm² (24 AWG) 
Note: 
 Cable length should not exceed more than 60m/200' with return line. 
Connections 
Correct connection of the units to the power supply will decrease the chances of units malfunctioning due to cabling 
problems. Please follow these basic rules. 
a)  Use the correct type & gauge of cable & connectors. 
b)  Keep cable runs as short as possible to reduce line loss. 
c)  Always use a return cable for each run. This will ensure balanced DC power to all units, that the line is correctly 
terminated, & all units receive power if one link of the chain is faulty. 
2.2  Operating the unit 
All the unit functions are accessed using the LED display & the three push-button switches on the rear panel. 










