Technical data
4. GENERAL REQUIREMENTS
CHLORIDE Active
UPS from 700 VA to 3000 VA
MKA4CAT0UKAG4/Rev. 1-07/2008
04
4.1 Standards and certifications
2006/95/EC and the EMC Directive 4.2 RoHS
2 0 0 4 / 10 8 / E C (s u p e r s e d i n g th e
Chloride operates with a Quality
Active voluntarily complies with the
Management System which complies
89/336/EEC, 92/31/EC and 93/68/EEC
requirements of the Directive 2002/95/EC
with ISO 9001:2000 for the design,
Directives).
regarding Restriction of the Use of Certain
man ufacture , sale , i nst all atio n,
Hazardous Substances (RoHS) in
m a i n t e n a n c e a n d s e r v i c e o f
Active is designed and manufactured in
Electrical and Electronic Equipment.
uninterruptible power supply systems.
acco r danc e wit h t h e foll owin g
The Chloride Environmental Policy and
4.3 Neutral/earth
international standards:
Management Systems comply with ISO
14001:2004 and Chloride is committed to
Active neutral output is not connected to
• EN62040-1-1, EN60950 (RD); general
implementing a policy of continuous
the earth and battery negative voltage is
and safety requirements.
improvement to production processes
referenced to neutral output.
• EN62040-2 Class C2, EMC requirements
and pollution reduction.
Active shall not modify the neutral state,
Active shall also bear the TÜV and UL/cUL
Active shall carry the CE mark in
with the exception in battery mode due to
certifications for safety.
the backfeed protection.
accordance with the Safety Directive
5. BATTERY MANAGEMENT
5.1 Battery configurations intervals can be configured via LCD replaced. This alarm can be deactivated by
display. the operator via front panel.
Active shall include the configurations The UPS shall automatically detect the
shown in the tables below: A pre-alarm signal shall be activated number of external battery packs
Batteries shall be sealed, lead-acid and before the end of battery back-up to alert connected via communication cables
maintenance-free. Internal batteries in the operator (BATTERY LOW signal). By (bundled with the battery packs)
the UPS are easy-swappable. UPS default, this signal shall be activated interconnected between the UPS and the
battery packs. Internal calculations about
back-up time are done according to the
quantity of battery packs connected. It is
recommended a maximum of 4 external
battery packs to each UPS.
Additional battery arrangements may be
configured, as well as external battery
chargers. Please check the details with
the local Chloride office for these
customized configurations.
5.2 Back-up times
The above battery configurations shall
provide the following back-up times.
includes internal protection against when the remaining battery capacity
overvoltages and deep discharge goes below 25% of the total capacity. This
They are typical back-up times assuming
protection to maximize reliable battery value can be configured by the user (via
resistive load, batteries fully charged and
life. LCD display) to 25%, 50% or 75%.
ambient temperature of 25ºC. These
values may vary depending on these
Test of battery system shall be run upon An end-of-battery-life alarm shall be
conditions. 700 VA model does not allow
user request (via front panel) or at regular activated 4 years after commissioning to
connection of external battery packs.
intervals (daily, weekly or monthly). These alert the operator that batteries should be
Battery Pack
BP-A1000/1500-T
BP-A1000/1500-RT
BP-A2000/3000-RT
Configuration
2x3x7.2Ah (36Vdc 14.4Ah)
2x3x7Ah (36Vdc 14Ah)
2x6x45W (72Vdc 90W)
UPS Model
Active 700T
Active 1000T/Active 1000RT
Active 1500T/Active 1500RT
Active 2000RT
Active 3000RT
Configuration
1x2x7.2Ah (24Vdc 7.2Ah)
1x3x7.2Ah (36Vdc 7.2Ah)
1x3x45W (36Vdc 45W)
1x6x7.2Ah (72Vdc 7.2Ah)
1x6x45W (72Vdc 45W)
1000 VA
models
UPS
UPS + 1BP
UPS + 2BP
UPS + 3BP
UPS + 4BP
160 W
37 min
158 min
254 min
397 min
476 min
400 W
15 min
55 min
97 min
174 min
220 min
560 W
11 min
38 min
69 min
99 min
161 min
800 W
6 min
25 min
46 min
67 min
89 min
700 VA
model
UPS
110 W
35 min
280 W
15 min
390 W
10 min
560 W
5 min
1500 VA
models
UPS
UPS + 1BP
UPS + 2BP
UPS + 3BP
UPS + 4BP
240 W
25 min
84 min
180 min
234 min
331 min
600 W
10 min
34 min
62 min
90 min
140 min
840 W
7 min
24 min
43 min
63 min
83 min
1200 W
3 min
16 min
28 min
42 min
56 min